290
(2) Ethernet communication is not possible when using a method other than
direct connection
If Ethernet communication is not possible in a method other than direct connection with the programming tool,
check the following items.
If Ethernet communication cannot be performed even after taking the above actions, the possible cause is a
failure of the connected device.
Check the items described in Page 290, Section 15.3.4 (3).
(3) Ethernet communication is not possible with the connected device
If Ethernet communication is not possible with the connected device, check the following items.
Check item Corrective action
IP addresses are overlapping.
Check the duplicate IP addresses using the Find CPU
function, and correct the IP addresses.
Correct the IP address of the programming tool (personal
computer) so that it differs from the address of the CPU
module.
Disconnect the device from the network, and ping the IP
address of the disconnected device. If there is any
response, the same IP address is used. Correct the IP
address.
The specified protocol is incorrect.
Correct the Transfer Setup setting."Ethernet Port Direct Connection" is selected.
The specified IP address or host name is incorrect.
Check item Corrective action
An error has occurred in a hub.
Remove the error from the hub.
*1
The setting on the connected device (personal computer) is
incorrect.
IP address setting
Ethernet port setting
Firewall setting
Communication setting of security software
Correct the setting on the connected device.
The SD/RD LED of the CPU module is not flickering during
communication.
Confirm the wiring.
IP addresses are overlapping.
Correct the IP address of the connected device so that it
differs from the address of the CPU module.
Disconnect the device from the network, and ping the IP
address of the disconnected device. If there is any
response, the same IP address is used. Correct the IP
address.
The ERR. LED turns on or flickers when power is resupplied.
Remove the error cause. (
Page 282, Section 15.2)
When parameters are read after switching to USB
connection, the Built-in Ethernet Port Setting is incorrect.
Correct the parameter.
In "Status of Each Connection" of "Ethernet Diagnostics",
MELSOFT Direct Connection is set to the forced deactivation
status.
Disable the forced deactivation.
In the "Error History" of "Ethernet Diagnostics", an error for
direct connection is detected.
Take corrective actions according to the error code.