Appendix 1 Error Codes
Appendix 1.4 List of error codes (2000 to 2999)
2410
[FILE OPE. ERROR]
• The specified program does not exist in the
program memory.
• This error may occur when the ECALL,
EFCALL, PSTOP, PSCAN, POFF or PLOW
instruction is executed.
• The specified file does not exist.
• A required file is not set in the PLC File tab of
"PLC Parameter".
■Collateral information
• Common information: File name/Drive name
• Individual information: Program error location
■Diagnostic timing
• When instruction executed
• Read individual information of the error
using the programming tool to identify the
numeric value (program error location).
Check the error step corresponding to the
value and correct it as necessary. Create
the specified file and write it to the CPU
module.
• If the specified file does not exist, write the
file to the target memory. Or correct the file
specification by a instruction.
• Set the required file in the PLC File tab of
"PLC Parameter".
RUN: Off/On
ERR.:Flashing/On
CPU Status:
Stop/Continue
*1
Qn(H)
QnPH
QnPRH
QnU
LCPU
2411
[FILE OPE. ERROR]
• The file cannot be specified by the program,
such as comment file.
• The specified program exists in the program
memory, but has not been registered in the
program setting of "PLC Parameter". This error
may occur when the ECALL, EFCALL, PSTOP,
PSCAN, POFF or PLOW instruction is
executed.
■Collateral information
• Common information: File name/Drive name
• Individual information: Program error location
■Diagnostic timing
• When instruction executed
Read individual information of the error using
the programming tool to identify the numeric
value (program error location). Check the
error step corresponding to the value and
correct it as necessary.
RUN: Off/On
ERR.:Flashing/On
CPU Status:
Stop/Continue
*1
Qn(H)
QnPH
QnPRH
QnU
LCPU
2412
[FILE OPE. ERROR]
This SFC program file cannot be specified with the
program.
■Collateral information
• Common information: File name/Drive name
• Individual information: Program error location
■Diagnostic timing
• When instruction executed
Read individual information of the error using
the programming tool to identify the numeric
value (program error location). Check the
error step corresponding to the value and
correct it as necessary.
RUN: Off/On
ERR.:Flashing/On
CPU Status:
Stop/Continue
*1
Qn(H)
QnPH
QnPRH
QnU
LCPU
2413
[FILE OPE. ERROR]
The file specified in the program was not written.
■Collateral information
• Common information: File name/Drive name
• Individual information: Program error location
■Diagnostic timing
• When instruction executed
Read individual information of the error using
the programming tool to identify the numeric
value (program error location). Check the
error step corresponding to the value and
correct it as necessary.
Check to ensure that the designated file has
not been write protected.
RUN: Off/On
ERR.:Flashing/On
CPU Status:
Stop/Continue
*1
Qn(H)
QnPH
QnPRH
2500
[CAN'T EXE. PRG.]
• Any of the program files are using a device that
is out of the range configured in the Device tab
of "PLC Parameter".
• After changing the device setting in "PLC
Parameter", only the parameters were written to
the CPU module.
• Although an SFC program exists, the number of
step relay points is insufficient in the Device tab
of "PLC Parameter".
■Collateral information
• Common information: File name/Drive name
• Individual information: -
■Diagnostic timing
• At power-on/At reset/STOP RUN
• Read the common information of the error
using the programming tool to identify the
numeric value (file name). Verify the device
assignments of the program file
corresponding to the value with its
parameter setting, and correct them as
necessary.
• Whenever a device setting is changed,
write both the parameter and program file
to the CPU module.
• To use the SFC program, set the number of
step relay points to appropriate value.
RUN: Off
ERR.:Flashing
CPU Status:Stop
QCPU
LCPU
[CAN'T EXE. PRG.]
• After changing the index modification setting in
"PLC Parameter", only the parameters were
written to the CPU module.
■Collateral information
• Common information: File name/Drive name
• Individual information: -
■Diagnostic timing
• At power-on/At reset/STOP RUN
• Whenever an index modification setting is
changed in "PLC Parameter", batch-write
the parameter and program file to the CPU
module.
RUN: Off
ERR.:Flashing
CPU Status:Stop
QnU
LCPU
Error
code
Error and cause Corrective action
LED status,
CPU status
Corresponding
CPU