EasyManua.ls Logo

Mitsubishi Electric Q26UD(E)HCPU - Page 364

Mitsubishi Electric Q26UD(E)HCPU
720 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
362
3015
[PARAMETER ERROR]
In a multiple CPU system configuration, the CPU
verified is different from the one set in the
parameter setting.
Collateral information
Common information: File name/Drive name
Individual information: Parameter number/CPU
No.
Diagnostic timing
At power-on/At reset/STOP RUN/At writing to
programmable controller
Read the individual information of the error
using the programming tool to identify the
numeric value (parameter No./CPU No.).
Check the parameters and its configuration
corresponding to the value, and correct them
as necessary.
RUN: Off
ERR.:Flashing
CPU Status:Stop
QnU
3016
[PARAMETER ERROR]
The CPU module incompatible with multiple CPU
synchronized boot-up is set as the target for the
synchronized boot-up in the [Multiple CPU
synchronous startup setting].
Collateral information
Common information: File name/Drive name
Individual information: Parameter number/CPU
No.
Diagnostic timing
At power-on/At reset
Delete the CPU module incompatible with
multiple CPU synchronized boot-up from the
setting.
RUN: Off
ERR.:Flashing
CPU Status:Stop
QnU
3040
[PARAMETER ERROR]
The parameter file is damaged.
Collateral information
Common information: -
Individual information: -
Diagnostic timing
At power-on/At reset
Write the parameters configured in "PLC
parameter" and "Network parameter" and
remote password to a parameter-valid drive,
and power on the system again or reset the
CPU module.
If the same error occurs, the cause is a
hardware failure. Please consult your local
Mitsubishi representative.
RUN: Off
ERR.:Flashing
CPU Status:Stop
Qn(H)
QnPH
QnPRH
3041
[PARAMETER ERROR]
Parameter file of intelligent function module is
damaged.
Collateral information
Common information: -
Individual information: -
Diagnostic timing
At power-on/At reset
Write the intelligent function module
parameter to the parameter-valid drive, and
power on the system again or reset the CPU
module.
If the same error occurs, the cause is a
hardware failure. Please consult your local
Mitsubishi representative.
RUN: Off
ERR.:Flashing
CPU Status:Stop
Qn(H)
QnPH
QnPRH
3042
[PARAMETER ERROR]
The system file that have stored the remote
password setting information is damaged.
Collateral information
Common information: -
Individual information: -
Diagnostic timing
At power-on/At reset
Write the parameters configured in "PLC
parameter" and "Network parameter" and
remote password to a parameter-valid
drive,
and power on the system again or
reset the CPU module. If the same error
occurs, the cause is a hardware failure.
Please consult your local Mitsubishi
representative.
When a valid drive for parameter is set to
other than [program memory], set the
parameter file (PARAM) at the boot file
setting to be able to transmit to the program
memory. Write the parameters configured
in "PLC parameter" and "Network
parameter" and remote password to a
parameter-valid drive, and power on the
system again or reset the CPU module. If
the same error occurs, the cause is a
hardware failure. Please consult your local
Mitsubishi representative.
RUN: Off
ERR.:Flashing
CPU Status:Stop
Qn(H)
QnPH
QnPRH
Error
code
Error and cause Corrective action
LED status,
CPU status
Corresponding
CPU

Table of Contents

Related product manuals