363
APPENDICES
A
Appendix 1 Error Codes
Appendix 1.5 List of error codes (3000 to 3999)
3100
[LINK PARA. ERROR]
In a multiple CPU system, the CC-Link IE module
controlled by another CPU is specified as the start
I/O number of the CC-Link IE module.
Collateral information
Common information: File name/Drive name
Individual information: Parameter number
Diagnostic timing
At power-on/At reset/STOP RUN
Delete the network parameter of the CC-
Link IE module controlled by another CPU.
Change the setting to the start I/O number
of the CC-Link IE module controlled by host
CPU.
RUN: Off
ERR.:Flashing
CPU Status:Stop
Qn(H)
QnPRH
QnU
[LINK PARA. ERROR]
The network parameter of the CC-Link IE
operating as the normal station is overwritten to
the control station. Alternatively, the network
parameter for the CC-Link IE module that is
operating as a normal station has been changed
to the control station. (The network parameter is
updated on the module by resetting.)
Collateral information
Common information: File name/Drive name
Individual information: Parameter number
Diagnostic timing
At power-on/At reset/STOP RUN
Reset the CPU module.
Qn(H)
QnPH
QnPRH
QnU
LCPU
[LINK PARA. ERROR]
The number of modules actually mounted is
different from that is set in Network parameter
for the CC-Link IE module.
The start I/O number of the actually mounted
module is different from the one set in the
network parameter of the CC-Link IE.
Parameter-set data cannot be used.
The network type of CC-Link IE is overwritten
during power-on. (When changing the network
type, switch RESET to RUN.)
Collateral information
Common information: File name/Drive name
Individual information: Parameter number
Diagnostic timing
At power-on/At reset/STOP RUN
Check the network parameters and actual
mounting status, and if they differ, make
them matched. If any of the network
parameters is corrected, write it to the CPU
module.
Check the set number of extension base
units.
Check the connection status of the
extension base units and extension cables.
Check the connection of the GOT if it is
bus-connected to the main base unit or
extension base unit.
If an error occurs even after taking the above
measures, the cause is a hardware failure.
Please consult your local Mitsubishi
representative.
[LINK PARA. ERROR]
The CC-Link IE module is specified for the start
I/O number of network parameter in the
MELSECNET/H.
The MELSECNET/H module is specified for the
start I/O number of network parameter in the
CC-Link IE.
Collateral information
Common information: File name/Drive name
Individual information: Parameter number
Diagnostic timing
At power-on/At reset/STOP RUN
Check the network parameters and actual
mounting status, and if they differ, make
them matched. If any of the network
parameters is corrected, write it to the CPU
module.
Check the set number of extension base
units.
Check the connection status of the
extension base units and extension cables.
Check the connection of the GOT if it is
bus-connected to the main base unit or
extension base unit.
If an error occurs even after taking the above
me
asures, the cause is a hardware failure.
Please consult your local Mitsubishi
representative.
Qn(H)
QnPH
QnPRH
QnU
Error
code
Error and cause Corrective action
LED status,
CPU status
Corresponding
CPU

Table of Contents

Related product manuals