440
4A28
H
IP
communication
test related
error
In the system where the CPU module is
connected to the request destination device
over Ethernet, the request path and the
response path of IP packets differ.
When multiple CC-Link IE modules with the
same network number are connected in a
multiple CPU system, the module mounted on
the lowest slot number is not set as a
controlled module that transfers IP packets.
When multiple CC-Link IE modules with the
same network number are connected in a
single or multiple CPU system, the station
number of the module mounted on the lowest
slot number is not set as a relay station
number in routing parameter.
Correct the routing parameter setting so that IP
packets use the same path for both request and
response transmission.
When multiple CC-Link IE modules with the
same network number are connected in a
multiple CPU system, set the module mounted
on the lowest slot number as a controlled
module that transfers IP packets.
When multiple CC-Link IE modules with the
same network number are connected in a single
or multiple CPU system, set the station number
of the module mounted on the lowest slot
number as a relay station number in routing
parameter.
QCPU
LCPU
4A29
H
IP
communication
test related
error
The 3rd byte (Network No.) of the IP address of
the request destination device overlapped with
the 3rd byte of the IP address of the CPU module
connected to the request source device by
Ethernet.
Check and correct the IP address settings of the
built-in Ethernet ports of the CPU module.
Check and correct the IP address of the request
destination device.
QCPU
LCPU
4A2A
H
IP
communication
test related
error
The IP address of a device on the CC-Link IE
network, the Built-in Ethernet port QCPU, or the
Built-in Ethernet port LCPU is not specified.
Specify the IP address of a device on the CC-Link
IE network, the Built-in Ethernet port QCPU, or the
Built-in Ethernet port LCPU.
QCPU
LCPU
4B00
H
Target-related
error
An error occurred in the access destination or
relay station.
The specified transfer setup (request
destination module I/O number) is illegal.
Take corrective action after checking the error
that occurred at the specified access destination
or the relay station to the accessed station.
Check the transfer setup (request destination
module I/O number or programmable controller
number) in the request data of the MC protocol,
etc.
Check the occurring stop error and take the
action.
QCPU
LCPU
4B01
H
Target-related
error
The target is not the No. 1 CPU of the multiple
CPU system.
Execute the request for the No. 1 CPU of the
multiple CPU system.
QCPU
4B02
H
Target-related
error
The request is not addressed to the CPU
module.
Perform operation for the module that can execute
the specified function.
QCPU
LCPU
4B03
H
Target-related
error
The specified route is not supported by the
specified CPU module version.
The communication target CPU module is not
mounted.
Check whether the specified route is supported
or not.
Check whether the CPU module is
mounted/connected or not.
Check the occurring stop error and take the
action.
QCPU
LCPU
4B04
H
Target-related
error
The specified transfer setup (request destination
module I/O number) is not supported.
In the target setup, an illegal value is set as the
start I/O number of the target module.
QCPU
4C00
H
Multiple CPU-
related error
The specified device is unavailable for the
motion CPU or outside the device range.
Check the request data contents. QCPU
4C08
H
Multiple CPU-
related error
There are a total of 33 or more DDWR and
DDRD requests.
Execute again after reducing the number of DDWR
and DDRD requests to be executed
simultaneously.
QCPU
4C09
H
Multiple CPU-
related error
The specification of the requested CPU module
No. is illegal.
Check the request data contents. QCPU
4C10
H
CPU module
data
backup/restorat
ion function
error
Maximum storable capacity is exceeded.
Maximum number of storable files is
exceeded.
Storable upper limit of the backup folder
number is exceeded.
Increase the free space of the SD memory card
and CPU module, and then execute the
processing again.
Delete files in the SD memory card and CPU
module, and then execute the processing again.
Delete backup data in the SD memory card, and
then execute the processing again.
QnUDV
Error code
(Hexadecimal)
Error item Error details Corrective action
Corresponding
CPU

Table of Contents