APPENDICES
A
Appendix 3 List of Special Register Areas
SD119
Battery life-
prolonging
factor
Battery life-
prolonging
factor
This register stores a value indicating a cause that has the
battery life-prolonging function enabled. While this register is
other than "0", the battery life-prolonging function is enabled.
S (Status
change)
New
QnU (except
QnUDV)
LCPU
SD130
to
SD137
Fuse blown
module
Bit pattern in
units of 16
points,
indicating the
modules
whose fuses
have blown
0: No
blown
fuse
1: Blown
fuse
present
This register stores the number of a fuse-blown output
module (in units of 16 points) in the following bit pattern. (If
the module numbers are set by parameter, the parameter-
set numbers are stored.)
For a module whose number of output points exceeds 16
points, only the bit corresponding to the output module
number within the number of output points occupied by the
module (in increments of 16 points) turns on.
Example: When a 64-point module is mounted on the slot 0,
only b0 turns on when the fuse has blown.
Not cleared even if the blown fuse is replaced with a new
one. The storage value is cleared by clearing the error.
S (Error) New Q00J/Q00/Q01
SD150
to
SD157
I/O module
verification
error
Bit pattern, in
units of 16
points,
indicating the
modules with
verify errors.
0: No
error
1: Error
If the status of the I/O module changes from that obtained at
power-on, the module No. (unit: 16 points) is stored in the
following bit pattern. (When I/O module numbers have been
set by the parameter, the parameter-set numbers are
stored.)
For a module whose number of I/O points exceeds 16 points,
only the bit corresponding to the I/O module number within the
number of I/O points occupied by the module (in increments of
16 points) turns on.
Example: When a 64-point module is mounted on the slot 0,
only b0 turns on when an error is detected.
Not cleared even if the blown fuse is replaced with a new
one. The storage value is cleared by clearing the error.
S (Error) New Q00J/Q00/Q01
SD180
Latest
volume of IP
packet
transferred
data
Latest
volume of IP
packet
transferred
data (lower
digits)
The latest value of total IP packet size (byte), which was
transferred per unit time (1 second), is stored.
Range: 0 to 4294967295 (FFFFFFFF
H
)
S (Status
change)
New
QnU
*5
LCPU
*6
SD181
Latest
volume of IP
packet
transferred
data (upper
digits)
Number Name Meaning Explanation
Set by
(When Set)
Corresponding
ACPU
D9
Corresponding
CPU
b15
b2
b1
b0
b0: CPU switch setting
0:No factor
1:Foctor
b1: Backup in execution by
latch data backup function
(to standard ROM)
to
Fixed to 0
b15
b14
b13
b12 b11
b10 b9 b8
b7
b6
b5 b4
b3
b2 b1
b0
000
1
(YC0)
000 00000000
1
(Y80)
SD130
00
1
(Y1F0)
0 0 0000 0000
1
(Y1A0)
SD131
00
00
1
(Y7B0)
00000 000
SD137
000
1
(Y730)
0
Indicates a fuse blown state.
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
000 000 0000000SD150
00 0 00000000SD151 0 0
0 0 0000 000SD157 0 000
00
00
00
1
()
X Y
7E0
1
()
X Y
0
1
()
X Y
190
Indicates an I/O module verify error.