PARAMETERS
89
4.2.23 Automatic restart after instantaneous power failure
(Pr. 57, Pr. 58, Pr. 162 to Pr. 165)
Pr. 57 "restart coasting time"
Pr. 58 "restart cushion time"
Pr.162 "Automatic restart after instantaneous power failure selection"
Pr.163 "First cushion time for restart"
Pr.164 "First cushion voltage for restart"
Pr.165 "Restart stall prevention operation level"
!
You can restart the inverter without stopping the motor (with the motor coasting) when the commercial
power supply is switched to the inverter operation or when the power is restored after an instantaneous
power failure. (When automatic restart operation is set to be enabled, UVT and IPF among the alarm
output signals will not be output at occurrence of an instantaneous power failure.)
Parameter
Number
Factory
Setting
Setting Range Remarks
57 9999 0, 0.1 to 5 s, 9999 9999: No restart
58 1.0 s 0 to 60 s
162 0 0, 1
0: Frequency
search
1: No frequency
search
163 0 s 0 to 20 s
164 0% 0 to 100%
165 150% 0 to 200%
STF
IM
NFB
CS
SD
CS
SD
S1 〈L
21
〉
R1 〈L
11
〉
T 〈L
3
〉
S 〈L
2
〉
R 〈L
1
〉
MC1
MC2
×
MC3
W
V
U
Connect CS-SD for use of only
automatic restart after instantaneous
power failure.
MC switching sequence
Instantaneous power failure time
Power supply (R, S, T)
Motor speed
N (r/min)
Inverter output
frequency
f (Hz)
Inverter output
voltage
E (V)
Coasting
time
speed
detection time
+
Pr. 57 setting
Cushion voltage time (value set in Pr. 58)
When Pr. 162=0 (with frequency search)
Coasting time
Pr. 57 setting.
Cushion voltage time
Pr. 58 setting
When Pr. 162=1 (without frequency search)
Instantaneous power failure time
Motor speed
N (r/min)
Inverter output
frequency
f (Hz)
Inverter output
voltage
E (V)
Power supply (R, S, T)
Approx. 5s
4