OPERATION/CONTROL
56
3.3.3 PU operation mode
(Operation using the operation panel (FR-DU04))
(
1
)
Operation at 60Hz
While the motor is running, repeat the following steps 2 and 3 to vary the speed:
Step Description Image
1
Power-on
Operation mode check
Switch power on and make sure that the operation command
indication "PU" is lit.
(If it is not lit, press the


MODE
key to choose the operation mode and
press the




key to switch to PU operation.)
ON











FR-DU04
CONTROL PANEL
Hz
MON EXT PU
A
V
REV FWD
2
Running frequency setting
Set the running frequency to 60Hz.
First, press the


MODE
key to select the frequency setting mode. Then,
press the




key to change the setting, and press the


SET
key
to write the frequency.
(or)










FR-DU04
CONTROL PANEL
Hz
MON EXT PU
A
V
REV FWD




3
Start
Press the


FWD
or


REV
key.
The motor starts running. The monitoring mode is automatically
selected and the output frequency is displayed.


REV


FWD
(or)










FR-DU04
CONTROL PANEL
Hz
MON EXT PU
A
V
REV FWD
4
Stop
Press the



STOP
RESET
key.
The motor is decelerated to a stop.













FR-DU04
CONTROL PANEL
Hz
MON EXT PU
A
V
REV FWD
(
2
)
PU jog operation
Hold down the


FWD
or


REV
key to perform operation, and release it to stop.
1) Set Pr. 15 "jog frequency" and Pr. 16 "jog acceleration/deceleration".
2) Select the PU jog operation. (Press the


MODE
key to choose the operation mode and press the




key
to switch to PU JOG operation.)
3) Hold down the


FWD
or


REV
key to perform operation.
(If the motor remains stopped, check Pr. 13 "starting frequency". The motor will not start if its setting is
lower than the starting frequency.)
3

Table of Contents