6.1 Standard Specifications
SPECIFICATIONS
203
6 SPECIFICATIONS
6.1 Standard Specifications
6.1.1 Model specifications
!
!!
!
200V class (Japanese version, NA version)
Type FR-A520-
""
K 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55
kW 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55
CT1/21 2 3 57.5101520253040506075
Applicable
motor capacity
(Note 1)
HP
VT 1 1.5 3 3 5 10 10 20 25 30 40 50 60 75 100
CT 1.1 1.9 3.1 4.2 6.7 9.2 12.6 17.6 23.3 29 34 44 55 67 82
Rated capacity
(kVA) (Note 2)
VT 1.3 1.9 3.7 4.6 7.1 10.7 14.1 20.7 25.9 30.5 39.2 49.7 58.4 70.8 94.6
CT 3 5 8 11 17.5 24 33 46 61 76 90 115 145 175 215
Continuous
current (A)
VT 3.6 5 9.6 12 18 28 37 54 68 80 104 130 154 185 248
CT 150% 60s, 200% 0.5s (inverse-time characteristics)
Overload
capacity (Note 3)
VT 120% 60s, 150% 0.5s (inverse-time characteristics)
Voltage (Note 4) Three phase, 200V to 220V 50Hz, 200 to 240V 60Hz
Three phase, 200V to
220V 50Hz,
200 to 230V 60Hz
Output
Regen-
erative
braking
torque
Maximum
value
/Permissi-
ble duty
15% torque/3%ED
(Note 5)
100%
torque/3%ED
(Note 5)
100%
torque/2%ED
(Note 5)
20% torque/continuous
Rated input AC
voltage, frequency
Three phase, 200V to 220V 50Hz, 200 to 240V 60Hz
Three phase, 200V to
220V 50Hz,
200 to 230V 60Hz
Permissible AC
voltage fluctuation
170 to 242V 50Hz, 170 to 264V 60Hz
170 to 242V 50Hz, 170 to
253V 60Hz
Permissible
frequency fluctuation
±
5%
Power supply
Power supply system
capacity (kVA) (Note 6)
1.52.54.55.59 121720283441526680100
Protective structure
(JEM 1030)
Enclosed type (IP20 NEMA1) (Note 7) Open type (IP00)
Cooling system Self-cooling Forced air cooling
Approx. weight (kg (lbs)),
with DU
2.0
(4.4)
2.5
(5.5)
3.5
(7.7)
3.5
(7.7)
3.5
(7.7)
6.0
(13.2)
6.0
(13.2)
8.0
(17.6)
13.0
(28.7)
13.0
(28.7)
13.0
(28.7)
30.0
(66.1)
40.0
(88.2)
40.0
(88.2)
55.0
(121.3)
Note: 1. The applicable motor capacity indicated is the maximum capacity applicable when Mitsubishi
4-pole standard motor is used.
2. The rated output capacity indicated assumes that the output voltage is 220V for 200V class and
440V for 400V class.
3. The overload capacity indicated in % is the ratio of the overload current to the inverter's rated
current. For repeated duty, allow time for the inverter and motor to return to or below the
temperatures under 100% load.
4. The maximum output voltage cannot exceed the power supply voltage. The maximum output
voltage may be set as desired below the power supply voltage. However, the crest value of the
inverter output voltage remains unchanged from the DC bus voltage.
5. Short duration rating 5s
6. The power supply capacity changes with the values of the power supply side inverter impedances
(including those of the input reactor and cables).
7. The open type (IP00) is used when the inboard option is fitted after removal of the option wiring
port cover.

Table of Contents