PROTECTIVE FUNCTIONS
198
!
!!
! Checking the inverter and converter modules
<Preparation>
(1) Disconnect the external power supply cables (R, S, T) 
〈
L
1
, L
2
, L
3
〉
 and motor cables (U, V, W).
(2) Prepare a meter. (Use 100
Ω
 range.)
<Checking method>
Change the polarity of the tester alternately at the inverter terminals R, S, T, U, V, W, P and N 
〈
L
1
, L
2
, L
3
, U,
V, W, 
+
 and 
−〉
, and check for continuity.
Note: 1. Before measurement, check that the smoothing capacitor is discharged.
2. At the time of continuity, the measured value is several to several ten’s-of ohms depending on the
module type, circuit tester type, etc. If all measured values are almost the same, the modules are
without fault.
<Module device numbers and terminals to be checked>
Tester Polarity Tester Polarity
Measured Value Measured Value
R 
〈
L
1
〉
P 
〈+〉
Discontinuity R 
〈
L
1
〉
N 
〈−〉
Continuity
D1
P 
〈+〉
R 
〈
L
1
〉
Continuity
D4
N 
〈−〉
R 
〈
L
1
〉
Discontinuity
S 
〈
L
2
〉
P 
〈+〉
Discontinuity S 
〈
L
2
〉
N 
〈−〉
Continuity
D2
P 
〈+〉
S 
〈
L
2
〉
Continuity
D5
N 
〈−〉
S 
〈
L
2
〉
Discontinuity
T 
〈
L
3
〉
P 
〈+〉
Discontinuity T 
〈
L
3
〉
N 
〈−〉
Continuity
Converter module
D3
P 
〈+〉
T 
〈
L
3
〉
Continuity
D6
N 
〈−〉
T 
〈
L
3
〉
Discontinuity
UP 
〈+〉
Discontinuity U N 
〈−〉
Continuity
TR1
P 
〈+〉
U Continuity
TR4
N 
〈−〉
U Discontinuity
VP 
〈+〉
Discontinuity V N 
〈−〉
Continuity
TR3
P 
〈+〉
V Continuity
TR6
N 
〈−〉
V Discontinuity
WP 
〈+〉
Discontinuity W N 
〈−〉
Continuity
Inverter module
TR5
P 
〈+〉
W Continuity
TR2
N 
〈−〉
W Discontinuity
(Assumes the use of an analog meter.)
D1 D2 D3
D4 D5 D6
TR1 TR3 TR5
TR4 TR6 TR2
U
V
W
R
〈L
1
〉
S
〈L
2
〉
T
〈L
3
〉
C
P 〈+〉
N 〈–〉
Inverter moduleConverter module