PARAMETERS
94
Pr. 60 "intelligent mode selection"
Related parameter
4.2.26  Acceleration/deceleration reference current/lift mode starting
frequency (Pr. 61 to Pr. 64)
Pr. 61 "reference I for intelligent mode"
Pr. 62 "ref. I for intelligent mode accel."
Pr. 63 "ref. I for intelligent mode decel."
Pr. 64 "starting frequency for elevator mode"
!
Set these parameters to improve performance in the intelligent mode.
Parameter
Number
Factory
Setting
Setting Range Remarks
61 9999 0 to 500A, 9999
9999: Referenced from rated inverter
current.
62 9999 0 to 200%, 9999
63 9999 0 to 200%, 9999
64 9999 0 to 200%, 9999
<Setting>
(
1
)
 Pr. 61 "reference I for intelligent mode"
Setting Reference Current
9999 (factory setting) Referenced from rated inverter current
0 to 500A Referenced from setting (rated motor current)
(
2
)
 Pr. 62 "ref. I for intelligent mode accel."
(The reference value differs between the shortest acceleration/deceleration mode and optimum
acceleration/deceleration mode.)
The reference current setting can be changed.
Setting Reference Current Remarks
150% (180%) is the limit value. Shortest acceleration/deceleration mode
9999 (factory setting)
100% is the optimum value. Optimum acceleration/deceleration mode
The setting of 0 to 200% is the limit value. Shortest acceleration/deceleration mode
0 to 200%
The setting of 0 to 200% is the optimum
value.
Optimum acceleration/deceleration mode
(
3
)
 Pr. 63 "ref. I for intelligent mode decel."
(The reference value differs between the shortest acceleration/deceleration mode and optimum
acceleration/deceleration mode.)
The reference current setting can be changed.
Setting Reference Current Remarks
150% (180%) is the limit value. Shortest acceleration/deceleration mode
9999 (factory setting)
100% is the optimum value. Optimum acceleration/deceleration mode
The setting of 0 to 200% is the limit value. Shortest acceleration/deceleration mode
0 to 200%
The setting of 0 to 200% is the optimum
value.
Optimum acceleration/deceleration mode
(
4
)
 Pr. 64 "starting frequency for elevator mode"
Setting Reference Current
9999 (factory setting) 2Hz is the starting frequency.
0 to 10Hz The setting of 0 to 10Hz is the starting frequency.
Note: Pr. 61 to Pr. 64 are only valid when any of "1 to 6" is selected for Pr. 60.