PARAMETERS
146
4.2.49 User group selection (Pr. 160, Pr. 173 to Pr. 176)
Pr. 160 "user group read selection"
Pr. 173 "user group 1 registration"
Pr. 174 "user group 1 deletion"
Pr. 175 "user group 2 registration"
Pr. 176 "user group 2 deletion"
•
 Pr. 160 "user group read selection" is used to limit the parameters which may be read.
•
 From among all parameters, a total of 32 parameters can be registered to two different user groups.
The registered parameters may only be accessed for reading and writing.
Other parameters than those registered to the user groups cannot be read.
Parameter
Number
Factory
Setting
Setting Range Remarks
160 0 0, 1, 10, 11
173 0 0 to 999
174 0 0 to 999, 9999 9999: Batch deletion
175 0 0 to 999
176 0 0 to 999, 9999 9999: Batch deletion
<Examples of use>
(1) Parameter registration to user group (when registering Pr. 3 to user group 1)
FR-DU04
CONTROL PANEL
Hz
MON EXT PU
A
V
REV FWD
FR-DU04
CONTROL PANEL
Hz
MON EXT PU
A
V
REV FWD
FR-DU04
CONTROL PANEL
Hz
MON EXT PU
A
V
REV FWD
FR-DU04
CONTROL PANEL
Hz
MON EXT PU
A
V
REV FWD
FR-DU04
CONTROL PANEL
Hz
MON EXT PU
A
V
REV FWD
Pr. 173 reading
SET
SET
1.5 s
The number of parameters 
registered for user setting 
appears.
Using the         key, 
choose the parameter number 
to be registered.
Pr. 3 is registered to user 
group 1.
Using the        key, 
move to the next parameter 
to be registered. 
Using the    key, make 
registration.
.....
Flickering
.....
.....
.....
SET
(2) Parameter deletion from user group (when deleting Pr. 5 from user group 1)
FR-DU04
CONTROL PANEL
Hz
MON EXT PU
A
V
REV FWD
FR-DU04
CONTROL PANEL
Hz
MON EXT PU
A
V
REV FWD
FR-DU04
CONTROL PANEL
Hz
MON EXT PU
A
V
REV FWD
FR-DU04
CONTROL PANEL
Hz
MON EXT PU
A
V
REV FWD
FR-DU04
CONTROL PANEL
Hz
MON EXT PU
A
V
REV FWD
Pr. 174 reading
SET
SET
1.5 s
The number of parameters 
registered for user setting 
appears.
Using the        key, 
choose the parameter number 
to be deleted.
Pr. 5 is deleted from user 
group 1.
Using the         key, 
choose the parameter to be 
deleted. 
Using the    key, make 
deletion.
.....
Flickering
.....
.....
.....
SET
(3) By setting the required value in Pr. 160, make the user groups valid or invalid.
Pr. 160 Setting Description
0 All parameters can be accessed for reading and writing (Factory setting)
1 Parameters registered to user group 1 may only be accessed for reading and writing.
10 Parameters registered to user group 2 may only be accessed for reading and writing.
11 Parameters registered to user groups 1 and 2 may only be accessed for reading and writing.
Note: 1. Pr. 77, Pr. 160 and Pr. 991 values can always be read independently of the user group setting.
2. When Pr. 173 or Pr. 174 is read, the number of parameters registered to user group 1 appears.
When Pr. 175 or Pr. 176 is read, the number of parameters registered to user group 2 appears.
3. "0" set in the second digit of the 2-digit Pr. 160 setting is not displayed. However, it is displayed
when "0" is set in the first digit only.
4. When "9999" is set in Pr. 174 or Pr. 176, the parameters registered to the corresponding user
group is batch-deleted.