EasyManua.ls Logo

Mitsubishi FR-A500 Series - OL Signal Output Timer (Pr. 157)

Mitsubishi FR-A500 Series
242 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PARAMETERS
145
Pr. 190 "RUN terminal function
selection"
Pr. 191 "SU terminal function selection"
Pr. 192 "IPF terminal function selection"
Pr. 193 "OL terminal function selection"
Pr. 194 "FU terminal function selection"
Pr. 195 "A, B, C terminal function
selection"
Related parameters
4.2.48 OL signal output timer (Pr. 157)
Pr. 157 "OL signal waiting time"
Use this parameter to set whether the overload alarm signal (OL signal) is output immediately or a preset
period of time after occurrence of an overload status.
Parameter
Number
Factory
Setting
Setting Range Remarks
157 0 0 to 25 s, 9999 9999: No signal output
Overload status (OL output)
OL output signal
Set time (s)
<Setting>
Refer to the following table and set the parameter:
Pr. 157
Setting
Description
0 Output immediately.
0.1 to 25 Output after the set time (s) has elapsed.
9999 Overload alarm signal is not output.
Pr. 158
'
''
'
Refer to Pr. 54.
4

Table of Contents

Related product manuals