PARAMETERS
153
Pr. 76 "alarm code output selection"
Pr. 79 "operation mode selection"
Related parameters
4.2.54 Programmed operation function (Pr. 200 to Pr. 231)
Pr. 200 "programmed operation minute/second
selection"
Pr. 201 to Pr. 210 "program set 1 1 to 10"
Pr. 211 to Pr. 220 "program set 2 11 to 20"
Pr. 221 to Pr. 230 "program set 3 21 to 30"
Pr. 231 "timer setting"
"
In programmed operation, automatic operation is performed under the control of the internal timer in
accordance with the preset time of day, running frequency and rotation direction.
"
This function is made valid when the following parameter is set to the following value:
•
 
Pr. 79 = "5" (programmed operation)
"
You can select the time unit for programmed operation between "minute/second" and "hour/minute".
"
The start time of day, rotation direction and running frequency are defined as one point and every 10 points
are grouped into three:
•
 
Group 1: Pr. 201 to Pr. 210
•
 
Group 2: Pr. 211 to Pr. 220
•
 
Group 3: Pr. 221 to Pr. 230
"
Use Pr. 231 to set the time of day when programmed operation is started.
Parameter
Number
Factory
Setting
Setting Range Remarks
200 0 0 to 3
0, 2 [minute/second]
1, 3 [hour/minute]
201 to 210 0,9999,0
0 to 2
0 to 400, 9999
0 to 99.59
0 to 2: Rotation direction
0 to 400, 9999: Frequency
0 to 99.59: Time
211 to 220 0,9999,0
0 to 2
0 to 400, 9999
0 to 99.59
0 to 2: Rotation direction
0 to 400, 9999: Frequency
0 to 99.59: Time
221 to 230 0,9999,0
0 to 2: Rotation direction
0 to 400, 9999: Frequency
0 to 99.59: Time
0 to 2: Rotation direction
0 to 400, 9999: Frequency
0 to 99.59: Time
231 0 0 to 99.59
<Wiring example>
•
 
For sink logic
STF
RH
RM
RL
STR
SD
FU
OL
PF
SU
SE
I
 1
 2
 3
 U,V,W
Output signal common
Programmed 
peration start
Group selection
imer reset
Input signal common
Inverter
Motor
Terminal function    Pr. 79 = 5
Terminal function    Pr. 76 = 
Group run signals
(Open collector)
Time-out signal
R,S,T
〈L
1
,L
2
,L
3
〉
4