PROTECTIVE FUNCTIONS
187
Operation Panel
Indication
E.PUE
FR-PU04
PU Leave Out
Name
Parameter unit disconnection
Description
This function stops the inverter output if communication between the inverter and
PU is suspended, e.g. the operation panel or PU is disconnected, when "2", "3",
"16" or "17" was set in Pr. 75 "reset selection/disconnected PU detection/PU stop
selection". This function stops the inverter output if the number of successive
communication errors is greater than the permissible number of retries when the
Pr. 121 value is "9999" for RS-485 communication from the PU connector. This
function stops the inverter output if communication is broken for the time set in
Pr. 122.
Check point
Check for loose fitting of the DU or PU.
Check the Pr. 75 setting.
Corrective action
Fit the DU and PU securely.
Operation Panel
Indication
E.RET
FR-PU04
Retry No Over
Name
Retry count exceeded
Description
If operation cannot be resumed properly within the number of retries set, this
function stops the inverter output.
Check point
Find the cause of alarm occurrence.
Corrective action
Eliminate the cause of the error preceding this error indication.
Operation Panel
Indication
E.LF
FR-PU04

Name
Output phase failure protection
Description
This function stops the inverter output if one of the three phases (U, V, W) on
the inverter
s output side (load side) results in open phase.
Check if the rated motor current is extremely lower than the rated inverter current.
Check point
Check the wiring (Check the motor for a fault).
Check that the capacity of the used motor is not smaller than the inverter capacity.
Corrective action
Check the cables properly.
Check the setting of Pr. 251 "output phase failure protection selection".
Operation Panel
Indication
E.CPU
FR-PU04
CPU Fault
Name
CPU error
Description
If the arithmetic operation of the built-in CPU does not end within a predetermined
period, the inverter self-determines it as an alarm and stops the output.
Check point

Corrective action
Make connection securely.
Contact your sales representative.
Operation Panel
Indication
E. 1
to
E. 3
FR-PU04
Fault 1 to Fault 3
Name
Option fault
Description
The inverter output is stopped if a contact fault occurs at the connector between the
inverter and communication option, a fault of the communication option itself, etc.
occurs.
Check point
Check that the communication option is plugged in the connector securely.
(1 to 3 indicate the option slot numbers.)
Corrective action
Connect the communication option securely.
Contact your sales representative.