INSTALLATION AND WIRING
20
4) Sink logic type
In this logic, a signal switches on when a current flows out of the corresponding signal input terminal.
Terminal SD is common to the contact input signals. Terminal SE is common to the open collector
output signals.
R
STF
STR
SD
Current
R
RUN
SE
1
9
R
R
DC24V
AX40Inverter
Current flow related to
RUN signal
When using an external power supply for transistor output, use terminal PC as a common to prevent
misoperation caused by leakage current. (Do not connect terminal SD of the inverter with terminal 0V of
the external power supply. When using terminals PC-SD as a 24VDC power supply, do not install the
power supply in parallel outside the inverter. Doing so may cause misoperation due to leakage current.)