PARAMETERS
59
Func-
tion
Parameter
Number
Name Setting Range
Minimum
Setting
Increments
Factory Setting
EC Version
Refer
To
Page:
52 DU/PU main display data selection
0 to 20, 22, 23, 24, 25,
100
1085
53 PU level display data selection 0 to 3, 5 to 14, 17, 18 1 1 85
54 FM terminal function selection
1 to 3, 5 to 14,
17, 18, 21
1185
55 Frequency monitoring reference 0 to 400Hz 0.01Hz 60Hz
50Hz
88
Display functions
56 Current monitoring reference 0 to 500A 0.01A Rated output current 88
57 Restart coasting time 0, 0.1 to 5 s, 9999 0.1 s 9999 89
Automatic
restart
functions
58 Restart cushion time 0 to 60 s 0.1 s 1.0 s 89
Additional
function
59 Remote setting function selection 0, 1, 2 1 0 91
60 Intelligent mode selection 0 to 8 1 0 92
61 Reference I for intelligent mode 0 to 500A, 9999 0.01A 9999 94
62 Ref. I for intelligent mode accel. 0 to 200%, 9999 0.1% 9999 94
63 Ref. I for intelligent mode decel. 0 to 200%, 9999 0.1% 9999 94
64 Starting frequency for elevator mode 0 to 10Hz, 9999 0.01Hz 9999 94
65 Retry selection 0 to 5 1 0 95
66
Stall prevention operation level reduction
starting frequency
0 to 400Hz 0.01Hz 60Hz
50Hz
77
67 Number of retries at alarm occurrence 0 to 10,101 to 110 1 0 95
68 Retry waiting time 0 to 10 s 0.1 s 1 s 95
69 Retry count display erasure 0

095
70 Special regenerative brake duty
0 to 15%/0 to 30%/0%
(Note 10)
0.1% 0% 80
71 Applied motor
0 to 8, 13 to 18, 20, 23,
24
1097
72 PWM frequency selection 0 to 15 1 2 98
73 0-5V/0-10V selection 0 to 5, 10 to 15 1 1 99
74 Filter time constant 0 to 8 1 1 100
75
Reset selection/disconnected PU
detection/PU stop selection
0 to 3, 14 to 17 1 14 100
76 Alarm code output selection 0, 1, 2, 3 1 0 102
77 Parameter write disable selection 0, 1, 2 1 0 103
78 Reverse rotation prevention selection 0, 1, 1 0 104
Operation selection functions
79 Operation mode selection 0 to 8 1 0 105
80 Motor capacity 0.4 to 55kW, 9999 0.01kW 9999 108
81 Number of motor poles 2, 4, 6, 12, 14, 16, 9999 1 9999 108
82 Motor exciting current (Note 4) 0 to , 9999 1 9999 109
83 Rated motor voltage 0 to 1000V 0.1V 200/400V (Note 2) 109
84 Rated motor frequency 50 to 120Hz 0.01Hz 60Hz
50Hz
109
89 Speed control gain 0 to 200.0% 0.1% 100% 108
90 Motor constant (R1) (Note 4) 0 to, 9999 9999 109
91 Motor constant (R2) (Note 4) 0 to, 9999 9999 109
92 Motor constant (L1) (Note 4) 0 to, 9999 9999 109
93 Motor constant (L2) (Note 4) 0 to, 9999 9999 109
94 Motor constant (X) (Note 4) 0 to, 9999 9999 109
95 Online auto tuning selection 0, 1 1 0 116
Advanced magnetic flux vectorcontrol
96 Auto tuning setting/status 0, 1, 101 1 0 109
100 V/F1 (first frequency) (Note 1) 0 to 400Hz, 9999 0.01Hz 9999 118
101 V/F1 (first frequency voltage) (Note 1) 0 to 1000V 0.1V 0 118
102 V/F2 (second frequency) (Note 1) 0 to 400Hz, 9999 0.01Hz 9999 118
103 V/F2 (second frequency voltage) (Note 1) 0 to 1000V 0.1V 0 118
104 V/F3 (third frequency) (Note 1) 0 to 400Hz, 9999 0.01Hz 9999 118
105 V/F3 (third frequency voltage) (Note 1) 0 to 1000V 0.1V 0 118
5-point flexible V/F
characteristics
106 V/F4 (fourth frequency) (Note 1) 0 to 400Hz, 9999 0.01Hz 9999 118
Parameter List