6 FX3U-64CCL setting (switch setting)
6.2 Transmission rate setting, hardware test
32
FX3U-64CCL User's Manual
6.2 Transmission rate setting, hardware test
Set the transmission rate or execute the hardware test using the "COM SETTING: B RATE" rotary switch
(Setting range: 0 to 4 and A to E) provided in the lower left position.
→ For details on the rotary switch layout, refer to Section 6.1.
For the hardware test, refer to the following.
→ For details on the hardware test, refer to Subsection 5.2.2.
Caution
Set the transmission rate within the specification of the maximum transmission distance and transmission
rate, along with the transmission rate selected in the master station.
6.3 Number of occupied stations, expanded cyclic setting
Set the number of occupied stations and expanded cyclic transmission using the "COM SETTING: STATION"
rotary switch (Setting range: 0 to 9 and C) provided in the lower right position.
→ For the rotary switch layout, refer to Section 6.1.
*1. For single expanded cyclic setting intelligent device station becomes Ver.1. For double, quadruple or
octuple expanded cyclic setting intelligent device station becomes Ver.2.
Caution
The number of occupied stations setting for the 64CCL affects the station number setting.
Setting Description Status
0 Transmission rate 156Kbps
Online
1 Transmission rate 625Kbps
2 Transmission rate 2.5Mbps
3 Transmission rate 5Mbps
4 Transmission rate 10Mbps
5 to 9 Unusable Unusable
A Transmission rate 156Kbps
Hardware test
B Transmission rate 625Kbps
C Transmission rate 2.5Mbps
D Transmission rate 5Mbps
E Transmission rate 10Mbps
F Unusable Unusable
Setting Number of occupied stations
Expanded cyclic setting
*1
01 station Single
1 2 stations Single
2 3 stations Single
3 4 stations Single
4 1 station Double
5 2 stations Double
6 3 stations Double
7 4 stations Double
8 1 station Quadruple
9 2 stations Quadruple
A, B Unusable Unusable
C 1 station Octuple
D to F Unusable Unusable