Setup Messages Chapter Five: Remote RS-232 Operation
88
How To Set the Set Point Values
The command [S x value] sets the values for the set points, where:
x: 1 = Set point A value
2 = Set point B value
3 = Set point C value
4 = Set point D value
5 = Set point E value
6 = Analog set point value
value:
set points A to E: % of full scale (with pressure control)
% of open (with position control)
analog set point: 0 = 0 to 100% of the controlling transducer’s
range (normal resolution - initial)
1 = 0 to 10% of the controlling transducer’s
range (10x normal resolution)
To set the value of set point A to 50% of full scale pressure, enter:
S 1 50
To report the value of a set point, issue the request:
R x
where x: 0 = Analog set point value
1 = Set point A value
2 = Set point B value
3 = Set point C value
4 = Set point D value
10 = Set point E value