Diagnostics
77
04/99 AWB 2700-1311 GB
Table 13: Diagnostic bit display
Table 14: Description of the diagnostic bits (Run/Ready)
LED Run/Ready Not Ready
.0.0 – –
.0.1 DDS ENR
0.2 DDK ERT
.0.3 DLS EDR
.0.4 DLK EPM
.0.5 DMC EWD
.0.6 DBM EDC
.0.7 DAC ECT
1.0 – EHM
1.1 – ECM
1.2 – ECL
1.3 – ETR
1.4 – EIL
1.5 – EOS
1.6 – ECA
1.7 – EAH
Code Meaning Description of the error
DDS Diagnostics
Remote status
Error in the status of a remote expansion
module. The basic unit’s Suconet K interface
has identified an error at one of the
networked stations. The error can be
located by checking the diagnostic byte of
each of the stations.
DDK Diagnostics
Remote
configuration
Error in the configuration of a remote
expansion module. Possible causes:
– Fewer Suconet stations than specified in
the topology configurator
– Fault in connection to station
– Data transmission error
DLS Diagnostics
Local status
Error in the status of a local expansion
module, e.g. digital outputs short-circuited.
H1311g.bk Seite 77 Freitag, 4. Juni 1999 1:12 13