Combi Modules
133
05/01 AWB2700-1384GB
10
Technical Data
Electronics module DP-16DI-P/16DO/0.5A-PK-ECO
Operating voltage (U
S
) 24 V DC
Permissible range 18 to 30 V DC
Indication LED green „RUN“
Operating current (I
S
) 70 mA
Field voltage 24 V DC
Permissible range 18 to 30 V DC
Indication LEDs green „U
L1
", „U
L2
"
Polarization protection no
Field current (no load) max. 20 mA per U
L
-supply
Potential separation to field bus 500 V
eff
/min
Inputs (Number) 16 (2x8)
Status '1'
U
H
min/max
I
H
min/max
15 V DC/30 Vd DC
1,2 mA/4 mA
Status '0'
U
L
min/max -5 Vdc/5 Vdc
Input delay approx. 3 ms
Indication LED green „17-32"
Outputs Number 16 (2x8) with byte-by-
byte field voltage supply
I
out
Short-circuit proof yes
Output delay < 100 µs (at R
L
F1 kΩ)
Lamp load max. 3 W
Indication LED green „1-16"
Diagnosis see chapter 8
Error diagnosis via the bus yes
Short-circuit yes
Field voltage yes
Ambient temperature
- Operating temperature
- Storage temperature
- Relative humidity
0 to +60 °C
-20 to +85 °C
15 to 95 % without dewing
EMC Interference immunity acc. to EN 50082-1 and 2