Technical Data
134
05/01 AWB2700-1384GB
Static electricity 8 kV air discharge, 6 kV relay discharge
acc. to EN 61000-4-2
Electromagnetic fields 10 V/m acc. to ENV 50140
Burst 2 kV acc. to EN 61000-4-4
communication interfaces
2 kV, acc. to IEC 801-4
HF unsymmetrical 10 V acc. to ENV 50141,
interference output acc. to EN 50081-2,
requirements acc. to EN 55011, group 1, class A. For
use in living areas (living, business and commercial
areas, small business) an individual authorization is
required
International protection class IP 20 (DIN 40050/IEC 144)
Base element
Measurement data VDE 0611
Part 1/8.92/IEC 947-7-1/ 1989
Rated voltage/current/cross section 250 V/17,5 A/1,5 mm
2
Rated surge voltage/contamination class 4 kV/3
Connection technology in TOP construction tension clamp
Connection technology 2/3-wire
Wire strip length 8 mm
Crimpable wire
-max. range
-“e“ single core H 07V-U
-“f“ thin core H 07V-K
-“f“ with ferrules acc. to DIN 46228/1 (ferrules crimped
gas-tight)
0,13 to 2,5 mm
2
0,5 to 2,5 mm
2
0,5 to 1,5 mm
2
0,5 to 1,5 mm
2
Plug gauge acc. to IEC 947 - 1/1988 A2
Continuous current on the ZVL distribution rail 17,5 A
General information
Width/Length/Height (mm) with TS 35 x 7,5
Base element/elec. module 2/3-wire 142/115/90
Weight 550 g,
g15 %