EasyManuals Logo

Monitronics VISTA-15PMT User Manual

Monitronics VISTA-15PMT
32 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #6 background imageLoading...
Page #6 background image
6
50 Burglary Dialer Delay [2,0]
Delay Time Delay Disable
Delay Time:
1 = 15 seconds; 2 = 30 seconds; 3 = 45 seconds
Provides delay of “BURGLARY ALARM” report to the central
station, which allows time for the subscriber to avoid a false
alarm transmission. This delay does not apply to zone type
24 alarms (silent burglary) or to 24-hour zone types 6, 7, and
8 (silent panic, audible alarm, auxiliary alarm), which are
always sent as soon as they occur.
Delay Disable:
0 = use delay set in entry 1
1 = dial delay disabled for zones listed in zone list 6 (use
zone list 6 to enter those zones that need dial delay to
be disabled; these zones ignore the setting in entry 1)
UL: Dial delay plus entry delay must not exceed one minute;
use zone list 6 to disable dial delay from appropriate zones,
if necessary.
53 SESCOA/Radionics Select [0]
0 = Radionics (0-9, B-F); enter “0” for all non-SESCOA formats
1 = SESCOA (0-9 only reporting)
54 Dynamic Signaling Delay [4]
Select delay from 0 to 225 secs, in 15-sec increments.
0 = no delay (both signals sent);
1 = 15 secs; 2 = 30 secs, etc.
Intended for reporting via a communication device on the ECP
bus (LRR). This field lets you select the time the panel should
wait for acknowledgment from the first reporting destination
(see 55) before it attempts to send a message to the second
destination. Delays can be selected from 0 to 225 seconds, in
15-second increments. This delay is per message. If 0 is
entered in this field, the control panel will send redundant
reports to both Primary Dialer and LRR.
UL: If using line security, must be “0; Reports will be sent to
both the dialer and the communication device.
55 Dynamic Signaling Priority / [0]
AAV Path Select
0 = Primary Dialer first / AAV via phone line
1 = Communication Device (LRR) first / AAV via
communication device path (see AAV paragraph below)
This field selects the primary communication path for
reporting (dialer or communication device) of primary phone
number events
(see 49 Split/Dual Reporting) and selects
the communication path used for AAV sessions (phone line
or communication device path). Use 29 IP/GSM menu
mode to enable the communication device being used.
† Reports intended for the secondary phone number are not
sent via the communication device.
For Dynamic Signaling Priority:
Select the initial reporting destination for messages:
Primary Dialer First selected (
0
):
If acknowledged before delay expires (see 54), then
message will not be sent via LRR.
If not acknowledged before delay expires, message is
sent to both the Primary Phone No. and via LRR.
Communication Device (LRR) First selected (
1
):
If acknowledged before delay expires, then message will
not be sent to the primary dialer.
If not acknowledged before delay expires, message is
sent to both the Primary Phone No. and via LRR.
For AAV Path Select:
If using the UVS system or AVS system with non-ECP
connection, option 0 must always be used.
If using the AVS system with ECP connection, either
option (0 or 1) may be used, but note the following:
IMPORTANT: If option “1” is selected, a 2-way voice (AAV)
device compatible with the communication device path must
be used (ex. GSMV communicator). When selected, AAV
sessions always occur via the GSMV communicator, even if
reporting reverts to phone line backup due to GSMV
communicator path reporting failure.
For UL Commercial Burglary installations that use a DACT
and LRR, this field must be “0”.
56,
57,
58 Menu Modes
These are Menu Mode commands, not data fields, for Zone
Programming, Function Key Programming, and Expert Mode Zone
Programming respectively. See respective sections later in this
document.
TO PROGRAM SYSTEM STATUS, & RESTORE REPORT CODES
(
59 thru
68, *70 thru
76, and
89):
For 3+1 or 4+1 Standard Format: Enter a code in the
first
box: 1–
9, #+10 for 0, #+11 for B, #+12 for C, #+13 for D, #+14 for E, #+15
for F.
A 0 (
not
#+10) in the
first
box will disable a report. A 0 (
not
#+10)
in the
second
box will result in automatic advance to the next field.
For Expanded or 4+2 Format: Enter codes in
both
boxes (1st and
2nd digits) for 1–9, 0, or B–F, as described above.
A 0 (
not
#+10) in the
second
box will eliminate the expanded
message for that report. A 0 (
not
#+10) in
both
boxes will disable
the report.
For Ademco Contact ID® Reporting: Enter any digit (other than 0)
in the
first
box, to enable zone to report (entries in the
second
boxes
are ignored).
A 0 (
not
#+10) in the
first
box disables the report.
UL: Report codes are required in fields *61, *65, *71, *72, for UL
Commercial Burglar Alarm installations.
Report codes are required in fields *60, *62, *63, *64, *70, *73, *74,
*75, *76, for UL Commercial Burglar Alarm installations and
required for Residential Fire Alarm installations
SYSTEM STATUS REPORT CODES (
59–
68)
59 Exit Error Alarm Report Code [1]
SIA NOTE: Always enabled. Sends both exit error and zone
alarm reports in the event of an exit error condition. Also see
field *69.
After arming the system, entry/exit and interior zones
remaining open after exit delay expires cause an alarm
sound at the keypad and external sounder (keypad also
displays “EXIT ALARM”), and entry delay begins. Disarming
before the end of the entry delay stops the alarm sounding
and no message is sent to the central station. The keypad
will display “CA” (fixed-word) or “ALARM CANCELED”
(alpha display).
If the system is not disarmed before entry delay expires, an
“EXIT ALARM” message and zone alarm message will be
sent to the central station. The keypad will display “EA”
(fixed-word ) or “EXIT ALARM” (alpha display), and alarm
sounding continues until the system is disarmed (or timeout
occurs).
An Exit Alarm condition will also result if a fault occurs in an
exit or interior zone within 2 minutes following the end of the
exit delay, and an “EXIT ALARM” message will be sent to
the central station (also see field *69 Recent Closing report).
With Contact ID format, the message will contain the zone
number and error code 374 (“ALARM–EXIT ERROR”).
60 Trouble Report Code [10] |
Sent if a zone has a trouble condition.
See UL System Reporting Note above *59.
61 Bypass Report Code [00] |
Sent when a zone is manually bypassed.
See UL System Reporting Note above *59.
62 AC Loss Report Code [10] |
Timing of this report is random with up to a 4-hour delay. If
AC restores before the report goes out, there is no “AC
LOSS” report.
See UL System Reporting Note above *59.
63 Low Bat Report Code [10] |
Sent when the system’s backup battery has a low-battery
condition. See UL System Reporting Note above *59

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Monitronics VISTA-15PMT and is the answer not in the manual?

Monitronics VISTA-15PMT Specifications

General IconGeneral
BrandMonitronics
ModelVISTA-15PMT
CategoryControl Unit
LanguageEnglish