Programmable Limit Alarm Trips
SPA
2
SECTION 4
Configuring the Analog Output (-AO Option)
Figure 4.10. gives an overview of the Analog Output Configuration menu.
If your unit is equipped with the -AO option, use this menu for configuration.
1. Press SELECT at the “CONFG AOUT” display. This sends you to the “SEL AOUT” section,
now press SELECT.
2. Once you reach the “SET DAMP” field, you may skip the damping parameter, by using the
Down button to reach the next field. To set damping, proceed to Step 3.
Damping– Output Damping allows you to introduce a delay (0-30sec) into the response of
your unit in order to stop momentary input variations from setting off alarms.
3. To set damping, press SELECT at the “SET DAMP” display. Use the UP and DOWN buttons
to enter a value between 0 and 30 seconds; press SELECT.
4. Press SELECT at “FAIL MODE” to program the setting. Choose “FAIL HIGH” or FAIL LOW”
if using HLPRG unit. Choose “FAIL HIGH”, “FAIL LOW”, “HOLD LAST”, “HOLD GO-HI”, or
“HOLD GO-LO” if using TPRG unit. This sends you to “EXIT AOUT”.
HIGH/LOW– Choosing either of these options will send the output to a High (23.6mA for current;
11.0V for voltage) or Low (3.6mA forcurrent; -0.5V for voltage), respectively. This can also be
translated as 90% of the output’s zero value.
HOLD LAST (TPRG) – This will display the last value present before the failure.
HOLD GO-HI/HOLD GO-LO (TPRG) – This will hold the last value before failure, for a set time,
and then return to the High or Low value, depending on configuration.
Figure 4.10. CONFG AOUT Menu
CONFG
AOUT
D
D
D
U
U
U
SEL
AOUT
SET
DAMP
FAIL
MODE
EXIT
AOUT
SEL
U
VOLT/
CURRENT
SEL
SEL
D
SCALE AOUT menu
SEL
XX
SEC
(XX = 0-30)
SEL
U
D
SEL
FAIL LOW
FAIL HIGH
HOLD LAST*
HOLD GO-HI*
HOLD GO-LO*
*TPRG UNITS
ONLY
SEL
U/D
SEL
TOGGLE