Programmable Limit Alarm Trips
SPA
2
SECTION 4
Fault Alarm Configuration
Figure 4.15 gives an overview of the Fault Alarm Configuration menu.
Fault alarms are set in order to notify you of any fault conditions during your process. If you wish an
alarm condition when a malfunction occurs, use the Fault Alarm
1. At the “CONFG ALARM” menu, press SELECT. Use the UP and DOWN buttons to toggle
between the alarms. When the desired alarm appears, press SELECT.
2. At the “ALARM TYPE” menu press SELECT. From here you will choose your alarm type. Use
the UP and DOWN buttons to scroll through the selections. Press SELECT once “ALARM
FAULT” is displayed.
Below are the configuration options you are given in setting up the fault alarm. You may
choose any combination of alarms including all three.
SENSR (HLPRG) / INPUT (TPRG) FAULT– You are notified upon breakdown of your input.
INPUT SAT– Should the input become overloaded or saturated, your alarm would activate.
SPA FAULT– Choosing this parameter activates the alarm at any failure that occurs in the
SPA
2
itself.
Note: Enabling all fault alarm configurations will activate the alarm at any failure that occurs
(refer to Table 6.1 in Section 6: Operation and Maintenance of this manual).
3. “INPUT/SENSR FAULT” appears. Press SELECT at “INPUT/SENSR FAULT”. Dependent
upon whether you wish the alarm activated due to an input fault, use the UP and DOWN
buttons to scroll through the “ALARM ON” and “ALARM OFF” options. Once you have made a
selection, press SELECT.
4. Press SELECT at the “INPUT SAT” display. You are given the choice of “ALARM ON” or
“ALARM OFF” by using the UP and DOWN buttons. Choose your setting and press SELECT.
5. Next, the “SPA FAULT” menu is displayed. Press SELECT. Toggle between “ALARM ON”
and “ALARM OFF” by using the UP and DOWN buttons and press SELECT when the setting
you desire is displayed.
6. Press SELECT at “ENTER DELAY” and enter your desired delay time by using the UP and
DOWN buttons.
7. At the “SET LATCH” display, press SELECT and choose “LATCH ON” or “LATCH OFF” using
the UP and DOWN buttons; press SELECT.
Refer to the “Trip Alarm Configuration” section for a description of delay and latching alarms.
8. Press SELECT at “SET FSAFE” to enter the menu. Then use the UP and DOWN buttons to
switch from “ALARM FSAFE” to “ALARM NONFS”. Make your selection and press SELECT.
Refer to the “Trip Alarm Configuration” section for a description of fail safe and non fail safe
alarms.