TROUBLE SHOOTING
To prevent risk of electric shock, trouble shooting should be done only by a qualified licensed electrician
__________________________________________________________________________________________________________________
Problem Probable Cause Suggested Remedy
__________________________________________________________________________________________________________________
No water in generator Water supply is "OFF" Turn on water supply
_
_______________________________________________________________________________________________________________
Clogged strainer Clean or replace strainer screen
_
_______________________________________________________________________________________________________________
Control voltage disconnected Restore control voltage
________________________________________________________________________________________________________________
Defective ON/OFF control switch Check/replace control switch
________________________________________________________________________________________________________________
Defective water solenoid valve Check/replace water solenoid valve
_
_______________________________________________________________________________________________________________
Defective PC Board Check/replace PC Board
_
_______________________________________________________________________________________________________________
Water feed probe not functioning Check/replace water feed probe (Models 360-1400) and
probe isolator and/or MM150 (Models CU2000 & higher)
________________________________________________________________________________________________________________
Clogged isolator tube Check/replace isolator tube (models 360-1400)
__________________________________________________________________________________________________________________
Generator does not heat Power supply disconnected Restore power supply
________________________________________________________________________________________________________________
No water in generator See above
________________________________________________________________________________________________________________
Hi-Limit pressure control tripped Clean out syphon tube & reset pressure control
________________________________________________________________________________________________________________
LWCO not functioning Check/replace LWCO probe
________________________________________________________________________________________________________________
Defective contactor Check/replace contactor
________________________________________________________________________________________________________________
Defective pressure control Check/replace control switch
________________________________________________________________________________________________________________
Defective PC Board Check/replace PC Board
________________________________________________________________________________________________________________
Defective heating element Check/replace heating element
__________________________________________________________________________________________________________________
Contactor chatters Defective PC board Check/replace PC Board
__________________________________________________________________________________________________________________
Generator floods Water feed solenoid Reverse solenoid connection
installed backwards CU 360-1400 Port “1” towards generator;
2" towards water supply
CU2000 and larger, “IN” port towards water supply
________________________________________________________________________________________________________________
Defective water solenoid valve Check/replace water solenoid valve
________________________________________________________________________________________________________________
Defective PC Board Check/replace board
________________________________________________________________________________________________________________
Water feed probe (Models 360-1400) Check/replace water feed probe
not functioning and isolator
________________________________________________________________________________________________________________
Clogged isolator tube Check/replace isolator tube (models 360-1400)
________________________________________________________________________________________________________________
MM 150
(Models CU 2000 and higher)
Clean out pipes under MM 150
is clogged Equalizing piping and float chamber
__________________________________________________________________________________________________________________
CU81600 rotates twice Jumper in (X) BRN & BLK Check/remove jumper (page 17)
terminals not removed
__________________________________________________________________________________________________________________