EasyManua.ls Logo

MSA fieldserver EZ Series - Connecting the R1 & R2 Ports; Wiring; Supported RS-485 Baud Rates by Protocol

MSA fieldserver EZ Series
61 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3.2 Connecting the R1 & R2 Ports
For the R1 Port only: Switch between RS-485 and RS-232 by moving the number 4 DIP Switch left for RS-485 and right
for RS-232 (see images in Section 3.1 DIP Switch Settings).
The R2 Port is RS-485.
Connect to the 3-pin connector(s) as shown below.
3.2.1 Wiring
RS-485 RS-232
BMS
RS-485 Wiring
Gateway Pin
Assignment
BMS
RS-485 Wiring
Gateway Pin
Assignment
RS-485 + TX + RS-232 - TX +
RS-485 - RX - RS-232 + RX -
GND GND GND GND
NOTE:Use standard grounding principles for GND.
3.2.2 Supported RS-485 Baud Rates by Protocol
The supported baud rates for either port is based on the protocol of the connected devices.
The following baud rates are supported for Modbus RTU:
2400, 4800, 9600, 19200, 38400, 57600, 76800, 115200
The following baud rates are supported for BACnet MS/TP:
9600, 19200, 38400, 76800, 115200
10 EZ Gateway Modbus to BACnet Start-up Guide

Table of Contents