EasyManua.ls Logo

MSA fieldserver EZ Series - Completing Device Profile Setup

MSA fieldserver EZ Series
61 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7.3.3 Completing Device Profile Setup
Click on the Edit button (pencil icon) next to the name of the profile to complete setup.
If a data map was loaded from a file created from the “Excel Profile Generator”, go to the Device Settings tab to enter the
Modbus and BACnet parameters.
NOTE:See Section 11.5 Address Types and Data Types for additional information on Address Type.
If using a BACnet State Table, click on the “State Table” tab to define the table and its variables.
NOTE:The Table Name field must be 14 characters or less. No commas allowed. The State Text field must be
50 characters or less. No commas allowed.
24 EZ Gateway Modbus to BACnet Start-up Guide

Table of Contents

Related product manuals