10 Troubleshooting
10.1 Communicating with the EZ Gateway Over the Network
Confirm that the network cabling is correct.
Confirm that the computer network card is operational and correctly configured.
Confirm that there is an Ethernet adapter installed in the PC’s Device Manager List, and that it is configured to run the
TCP/IP protocol.
Check that the IP netmask of the PC matches the EZ Gateway. The Default IP Address of the EZ Gateway is
192.168.2.X, Subnet Mask is 255.255.255.0.
Go to Start|Run
Type in “ipconfig”
The account settings should be displayed
Ensure that the IP Address is 102.168.2.X and the netmask 255.255.255.0
Ensure that the PC and EZ Gateway are on the same IP Network, or assign a Static IP Address to the PC on the
192.168.2.X network.
EZ Gateway Modbus to BACnet Start-up Guide 45