EasyManua.ls Logo

MSA fieldserver ProtoNode - Checking Wiring and Settings

MSA fieldserver ProtoNode
46 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9.3 Checking Wiring and Settings
No COMS on Modbus RTU side. If Tx/Rx are not flashing rapidly then there is a COM issue on the Modbus side. To fix
this problem, check the following:
Visual observations of LEDs on ProtoNode. (Section 9.5 LED Functions)
Check baud rate, parity, data bits, stop bits
Check Modbus device address
Verify wiring
Verify all the Modbus RTU devices were discovered in Web Configurator. (Section 7 Configure the FieldServer)
No COMS on Modbus TCP/IP side. To fix, check the following:
Visual observations of LEDs on ProtoNode (Section 9.5 LED Functions)
Check device address
Verify wiring
Verify all the Modbus TCP/IP devices were discovered in Web Configurator (Section 7 Configure the FieldServer)
Field COM problems:
If Ethernet protocols are used, observe Ethernet LEDs on the ProtoNode (Section 9.5 LED Functions)
Visual dipswitch settings (using correct baud rate and device instance)
Verify IP Address setting
Verify wiring
NOTE:If the problem persists, a Diagnostic Capture needs to be taken and sent to support. (Section 9.4 Taking
a FieldServer Diagnostic Capture)
26 ProtoNode Start-up Guide

Table of Contents

Related product manuals