MI.NET MULTI-NETWORK COLLECTOR
46
Installation and Operation Manual
2.1 Gateway SWR fault:
(Status 3 LED =Red)
Action: Check all RF cable connections from Gateway module to remote amplifier
Problem solved? Yes -> Done
No -> Check/replace Antenna surge protector, MS-RC-HUB-SP
Problem solved? Yes -> Done
No -> Check/replace antenna cable between collector and remote amplifier
Problem solved? Yes -> Done
No -> Replace amplifier, MS-RC-HUB-amplifier
Problem solved? Yes -> Done
No -> Replace Gateway, MS-RC-HUB-GA
Problem Solved? Yes -> Done
No -> Repeat Section 2.1
End Section 2.1
2.2 Antenna SWR fault:
(Status 3 LED = Yellow)
Action: Check all cable connections between remote amplifier and antenna
Problem solved? Yes -> Done
No -> Check/replace surge protector on amplifier
Problem solved? Yes -> Done
No -> Replace amplifier, MS-RC-HUB-amplifier
Problem solved? Yes -> Done
No -> Replace antenna
Problem solved? Yes -> Done
No -> Contact Mueller Systems
End Section 2.2