ComDryControlSystem
2.1.1Internalcontrollingsensor
Theinternalhumiditysensoristhecontrollingsensorasdefault.Thisisindicatedbya(*)beforethereading
inthedisplay(*RH1…/*D1…/*X1…).
2.1.2Externalcontrollingsensor
Optionally,anexternalsensorcanbeconnected.ItwillautomaticallybedesignatedRH2/D2/X2)bythe
system.Whenconnected,itispossibletochooseexternalsensorascontrol.Thedisplaywillthenshow
(*RH2.../*D2.../*X2…).
Withanexternalsensorsetascontrolsensor,itispossibletodisconnectandreconnecttheexternalsensor
withoutlosingthecontrolsetting,e.g.[*RH2…]whiletheunitisswitchedoff(butpowered).When
switchedon,thesystemmakesveattempts(during20seconds)tocontacttheexternalcontrollingsensor.
Ifthisfails,thesystemrevertstotheinternalRH1-sensor.Subsequentlyanyrenewedassignmentofthe
externalsensorascontrolmustbecarriedoutmanually.
2.2Runtime
Runtimeisregisteredaslongastheprocessairfanisoperating.Itstopscountingwhentheunitisinstand
bymodeorisswitchedoff.Thesystemhastworuntimecounters,oneresettabletripmeterandone
non-resettabletotalruntimecounter.
Displayview
DescriptionType
Settingoption
Runtimetripmeter
RESETTABLEYes/No
Totalruntime(Displayjumps
from“TOTAL”todisplayview
andback).
READONLY
Timetoservice
RESETTABLEYes/No
ServiceintervalADJUSTABLE
Every100hours
MEN-CDCS-A1808Menusandparameters11