Nabco Acusensor M - Sensitivity Adjustment (Switches 17-18)

Nabco Acusensor M
28 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
18 of 28
Acusensor M Installaon Manual www.NabcoEntrances.com
P/N C-00187 Rev 8-25-17




Note:  An Noise helps prevent false detecon caused by electrical noise or nearby light sources.
Table 15 Anti-Noise
Anti-Noise
14 Description
Normal An Noise is OFF.
Special Use when a malfuncon occurs due to a lighng xture, or an electro magnec noise.




Table 16 Anti-Environment
Anti-Environment
15 16 Vibration * Mirror Snow Insect Note
Normal Inacve Inacve Inacve Inacve N/A
An-
Vibraon
Acve Inacve Inacve Inacve Use when Sensor malfuncons due to
door vibraon during operaon
An-Snow I Inacve Inacve Acve Acve Response me may slow down
An-Snow II Acve Acve * Acve ** Acve Select if no improvement is seen using
An-Vibraon and/or An-Snow I
* Response me may slow down
** Detecon Area narrows down
* Mirror is when Sensors are facing each other at a close distance.



Note:  The Sensivity Mode may be acvated for reasons such as color/material of the oor or clothes.
Table 17 Sensitivity
Sensitivity
17 18 Mounting Height
H
(High)
X 98” thru 118” (2.5m thru 3.0m)
X Recommended Switch Seng for above mounng height
M
(Medium)
X 79” thru 98” (2.0m thru 2.5m)
X Recommended Switch Seng for above mounng height
L
(Low)
X 79” thru 98” (2.0m thru 2.5m)
X Use if sensivity is too HIGH with Switch Seng (M)