Chapter 4 LabVIEW RT Programming
cFP-20xx and cFP-BP-x User Manual 4-6 ni.com
In the RT Target: Access dialog box previously shown, all hosts in
the
site.com domain can target the RT Engine, with the exception
of all hosts in the
test.site.com domain. Additionally, the hosts
a.test.site.com, b.test.site.com, and 130.164.123.123 also
can target the RT Engine. The host
public.site.com does not have
access, even though it is in the
site.com domain.
The default RT Target: Access settings permit any host machine to target
the RT Engine on the cFP-20xx without a password.
Note If the cFP-20xx does not have access to a Domain Name Server (DNS), do not use
domain name entries in the RT Target Access List. Requests to resolve domain names to
IP addresses fail and slow down the system. Place frequently matched entries toward the
bottom of the RT Target Access List to improve system performance.
RT Target: Miscellaneous
Use RT Target: Miscellaneous options to launch LabVIEW RT
applications at system startup and to specify the Downloaded VI Path.
Complete the following steps to open the RT Target: Miscellaneous
dialog box:
1. Target LabVIEW RT to the cFP-20xx. Refer to the Targeting LabVIEW
RT to the cFP-20xx section for more information about targeting
LabVIEW RT to the cFP-20xx.
2. Select Tools»Network Options.
3. Select RT Target: Miscellaneous from the pull-down menu to see the
following dialog box.