Appendix B Specifications
© National Instruments Corporation B-3 cFP-20xx and cFP-BP-x User Manual
Physical Characteristics
Screw-terminal wiring............................ 16–26 AWG copper conductor
wire with 7 mm (0.28 in.) of
insulation stripped from the end
Torque for screw terminals .................... 0.5–0.6 N m (4.4–5.3 lb in.)
Weight.................................................... 278 g (9.8 oz)
Environmental
FieldPoint modules are intended for indoor use only. For outdoor use,
they must be placed inside a suitable enclosure.
Operating temperature............................ 25 to 60 °C
Storage temperature ...............................
40 to 85 °C
Humidity ................................................ 10 to 90% RH, noncondensing
Maximum altitude .................................. 2,000 m
Pollution Degree .................................... 2
Shock and Vibration
Operating vibration, random
(IEC 60068-2-64) ................................... 10–500 Hz, 5 g
rms
Operating vibration, sinusoidal
(IEC 60068-2-6)..................................... 10–500 Hz, 5 g
Operating shock
(IEC 60068-2-27)................................... 50 g, 3 ms half sine,
18 shocks at 6 orientations;
30 g, 11 ms half sine,
18 shocks at 6 orientations

Table of Contents