UPASS REACH | INSTALLATION GUIDE
Connections
17/35
3.5.2 READ DISABLE INPUT
The reading of the uPASS Reach can be completely disabled with the RDIS input. This
input is commonly used in combination with a sensor (e.g. inductive loop) that
detects the presence of a person or vehicle. Use always a relay contact to connect
the internal 5V to the RDIS input. When the RDIS input is unused the reader is
enabled.
Connections:
RDIS
Read disable input
5V
Internal 5V source for read disable input
Warning: Using an external 5V supply can damage the unit.
Read disable
input
Figure 19: Read disable input
3.5.3 GENERAL PURPOSE INPUTS
Three general purpose inputs are available on the uPASS Reach reader. They have
the function as described in the firmware manual.
Connections:
IN1
General purpose input 1 (active low)
IN2
General purpose input 2 (active low)
IN3
General purpose input 3 (active low)
GND
Ground
General purpose inputs
Figure 20: GPIO inputs