EasyManua.ls Logo

Nederman HV Control Panel EX Series - Transformer and Motor Configuration; T1 Control Transformer Voltage Settings

Nederman HV Control Panel EX Series
94 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
HV Control PanelEN
12
ConnectcablesaccordingtotheElectricalwiringdiagram.
1. PlaceandmounttheMSclosetoVAC/RBUUnit.
2. ConnectMotorcableW1terminal1,3,5.
3. ConnectMotorcableW3toterminal2,4,6LabelcableinbothendswithsignW3.
4. ConnectMotorcableW2terminal7,9,11.
5. ConnectMotorcableW4terminal8,10,12LabelcableinbothendswithsignW4.
6. TightenthePEwiresfromW1,W3togetherintoPEterminal.
7. TightenthePEwiresfromW2,W4togetherintoPEterminal.
8. ConnectMSSignalcableContacts13,14toterminalX1:1andterminalX1:2incontrol
cabinet.LabelSignalcableinbothendswithsignW101.
9. PullcableW126intoVAC/RBUcabinetandpullitintomotorconneconbox.
10. ConnectPTCsensorwirestoCableW126wireS1andS1.
11. LabelPTCsensorcableinbothendswithsignW126.
5.4.5 Installaon Motor Cable W3 and W4
ConnectcableaccordingtoElectricalwiringdiagram.
1. Openmotorconneconboxandidenesterminalboltsize.
2. PullcableW3intoVAC/RBUcabinetandpullitintomotorconneconbox.
3. Peelwiresandmountringcableshoeonwires.
4. TightenthewiresintoV1,U1,W1motorterminal.
5. PullcableW4intoVAC/RBUcabinetandpullitintomotorconneconbox.
6. TightenthewiresintoU2,W2,V2motorterminal.
7. TightenthePEwiresfromW3,W4togetherintoPEterminal.
5.4.6 Supplementary equipotenal
IfsupplementaryPotenalbondingisrequiredaccordingtolocalregulaons,connectitto
PEonBusbar.
5.4.7 T1 Control Transformer Voltage Sengs
NOTE! Inthesengstablesbelow,thereisacolumnforcustomerspecicsengs.See
also 17.
TransformersupplyvoltageCableismarkedwith(003).
Ifthepowersupplyisanothervoltage,forexample,230or460Volt,thetransformersupply
voltagecablemustbemovedtotheinputthatappliestothenewpowersupplyvoltage.
Whenchangingtoanotherpowersupplyvoltage,checkTable 5-12: T1 Primary Protecon
Auto Fuse F2 Seng
andadjustAutofuseF2tothenewcurrentseng.
The24VACoutputcanbeadjustedupordownbymovingthevoltagesupplycable004to
terminal-20,0V,+20V.Defaultisonterminal0V.
FillinthetablebelowaerconguraonofTransformerT1.
Table5-5:T1TransformerPrimaryInputSengandFuseF2Seng.
Alternave Seng Default (x) Parameter Customer Seng
230/(400)/460
SupplyvoltageCable(003)

Table of Contents

Related product manuals