10.6 ENVIRONMENTAL CHARACTERISTICS
UPS range 10kVA 15kVA 20kVA 25kVA 30kVA 40kVA 50kVA
Audible Noise with
100% / 50% Load
dBA 55/49 55/49 57/49 57/49 58/50 59/50 59/50
Operation temperature °C 0 – 40
Ambient Temperature
for Batteries
(recommended)
°C
20 – 25
Storage Temperature °C -25 - +70
Battery Storage Time at
Ambient Temperature
Max. 6 months
Max. altitude (above sea
level)
m 1000m (3300ft) without de-rating
Meter above sea level (m / ft) De-Rating Factor for Power
1500 / 4850 0.95
2000 / 6600 0.91
2500 / 8250 0.86
De-rating factor for use
at altitudes above
1000m sea level
according
( IEC 62040-3)
3000 / 9900 0.82
Relative Air-humidity
Max. 95% (non-condensing)
Accessibility Rear access Front access
Positioning Min. 20 cm rear space (required for fan)
Input and Output Power
Cabling
Rear side bottom Front side bottom
Efficiency AC-AC
(depending on power rating)
%
Load : 100 % 75 % 50% 25%
95.5% 95.5% 95% 94.5%
Eco-Mode efficiency at
100% load
% 98 %
10.7 STANDARDS
Safety IEC/EN 62040-1, IEC/EN 60950-1
Electromagnetic Compatibility
IEC/EN 62040-2, IEC/EN61000-3-2,
IEC/EN61000-6-2,
EMC Classification for 10kVA 15-50kVA
Emission Class C2 C3
Immunity Class C3
Performance IEC/EN62040-3
Product certification CE
Degree of protection IP 20