Menu Configuration
Table 6-1 Continued
MENU SUBMENU DESCRIPTION
OT.CF OUTPUT CONFIGURATION
0.1 Analog Output:
D: Disabled
E: Enabled
0.2 V: Voltage analog out
C: Current analog out
0.3 O: Proportional to reading
P: Proportional to Setpoint 1
0.4 D: Direct reading
R: Reverse acting
0.5 F: 0-10 V proportional
H: 0-5 V proportional
P.BND 0000 through 9999 PROPORTIONAL BAND
Select from 0000 through 9999
M.RST -1999 through 9999 MANUAL RESET
Select from -1999 through 9999
OT.S.O -1999 through 9999 OUTPUT SCALE AND OFFSET
2-coordinate format for scaling the analog
output
LK.CF LOCK OUT CONFIGURATION
SP.E=E Enable setpoint changes
SP.=D Disable setpoint changes
RS.=E Enable RESET button in run mode
RS.=D Disable RESET button in run mode