Setting the automatic heating control system
FIGHTER 410P
For the Installer
22
FIGHTER 410P is equipped with outdoor temperature
controlled automatic controls. This means the supply
temperature is regulated in relation to the current out-
door temperature.
The relationship between outside temperature and
flow temperature is set with the Heating curve selec-
tion and Heating curve offset knobs.
The diagram is based on the dimensioned outdoor
temperature in the area and the dimensioned supply
temperature of the heating system. When these two
values meet, the heating control’s curve slope can be
read.
Set the Heating curve offset accordingly. A suitable
value for floor heating is -1 and for radiator systems
-2.
Also see the section Room temperature.