May be due toHeat pump action.CauseAlarm text on
the display
Alarm
no.
See fault-tracing schedule page
51.
Controls the return sensor
(EP23-BT3)
Sensor not connected/defect-
ive
Sensor fault
EP23- BT2
38
(supply temperature sensor,
extra climate system 3)
See fault-tracing schedule page
51.
Shuts off cooling, Closes shunt
(QN18) for cooling.
Sensor BT64 not connected,
defective.
Sensor fault
EQ1–BT64
39
Motor protection on one
phase (Norway) machine has
probably blown.
45
Internal electrical addition is
blocked.
Temperature limiter has
tripped
The temperat-
ure limiter has
tripped
52
Check serial numberThe compressor stops, all relay
outputs are set to 0 V
Serial number and program
do not match
Incorrect pro-
gram
56
Compressor blocked.Serial number and program
do not match each other.
Incorrect pro-
gram
57
All relay outputs are set to 0 V.
See fault-tracing schedule on
page 52.
Blocking the relevant com-
pressor. Calculated flow temper-
ature is set to min supply line.
Communication with the in-
put card missing for 60 secs.
Communication
fault with PCA
input EB15
70
See fault-tracing schedule on
page 53.
Compressor (EB101) blocked.Communication with the base
card missing for 15 secs.
Communication
fault with PCA
base-AA2
71
- Check communication cablesAccessory is blocked.Communication with the ac-
cessory card missing for 15
secs.
Existing commu-
nication fault
with access-
ory".
73 -
95
- Check the setting of the
dipswitch.
- Check communication cablesAccessory is blocked.Communication with room
unit zone 1-4 missing for 60
secs.
Existing commu-
nication fault
with ”room
unit".
96 -
99
Check fuses, voltages to the
accessory card .
Accessory blocked.Temporary communication
fault HW comfort.
Com. error Acc -
QZ1
206
Check that the communication
cables are correctly connected.
Check the setting of the
dipswitch.
See relevant manual.Compressor blocked.See relevant manual.High pressure
alarm.
220
See relevant manual.Compressor blocked.See relevant manual.Low pressure
alarm.
221
See relevant manual.Compressor blocked.See relevant manual.Motor protec-
tion alarm.
222
See relevant manual.Compressor blocked.See relevant manual.Sensor fault.223
43Chapter 6 | TroubleshootingNIBE™ VVM 320

Table of Contents

Other manuals for Nibe VVM 320

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Nibe VVM 320 and is the answer not in the manual?

Nibe VVM 320 Specifications

General IconGeneral
Dimensions (HxWxD)1800 x 600 x 615 mm
Power Supply230 V
Frequency50 Hz
Protection classIP21
Compatible withNibe heat pumps
DisplayTouch display
Smart Home IntegrationYes, via NIBE Uplink
Operating temperature0°C to +45°C
Relative humidityMax. 95 %
TypeControl unit for heat pumps

Related product manuals