Current menus
Default settingsNameMenu
-400start tillsats4.9.3
12 hrsminimum run-
ning time
5.3.2
55 °Clowest temperat-
ure
1,0shunt amplifica-
tion
30 secsshunt waiting
time
Connections, accessory card
FunctionInput
boiler sensorX2:21-22
external blockingX2:23-24
FunctionOutput
External addition (burner)
permitted
K1
Mixing valve, closeK2
Mixing valve, openK3
External circulation pumpK4
Step controlled additional heat (AXC 40)
Address (dipswitch setting): 1110 1000
■
When DM is below the set start DM the additional
heat is started and steps in as the DM falls / steps out
as DM increases.
■
Time between step ins = 60 secs.
■
Time between step outs = 2 secs.
■
Additional heat is only allowed to step out when
heating is permitted and when the additional heating
is permitted in heating mode and the input for
blocking is not connected.
Current menus
Default settingsNameMenu
-400 GMstart tillsats5.3.6
100 GMdiff. between ad-
ditional steps
3max. step
Linear/binary
control
Connections, accessory card
FunctionInput
Block step controlled addi-
tional heat
X2:23-24
FunctionOutput
Step 1K1
Step 2K2
Step 3K3
Hot water circulation (AXC 40)
Address (dipswitch setting): 1001 0000.
Hot water circulation (HWC) GP11.
The circulation pump is active for a set operation and
downtime time during a selected period.
NotesFactory set-
ting
SettingMenu
Time when
HWC must
be active
OffPeriod 12.9.2
Time when
HWC must
be active
OffPeriod 2
Time when
HWC must
be active
OffPeriod 3
3 minRun time
12 minDowntime
OffActivating
hot water
comfort
5.2.4
27Chapter 4 | Description of functionsNIBE™ VVM 320