88 Unidrive M/HS Frame 5 to 6 Power Installation Guide
Issue Number: 9
Table 5-8 Losses @ 40°C (104° F) ambient with high IP insert installed
Model
Normal Duty Heavy Duty
Drive losses (W) taking into consideration any current
derating for the given conditions
Drive losses (W) taking into consideration any
current derating for the given conditions
2
kHz
3
kHz
4
kHz
6
kHz
8
kHz
12
kHz
16
kHz
2
kHz
3
kHz
4
kHz
6
kHz
8
kHz
12
kHz
16
kHz
200 V
05200250 188 194 201 212 222 240 262 186 195 201 214 226 247 256
400 V
05400270 118 118 119 124 132 152 183 127 120 123 129 137 162 187
05400300 140 159 174 200 225 268 304 152 159 176 210 239 295 310
575 V
05500030 32 42 52 71 92 133 173 23 32 41 58 76 112 148
05500040 70 85 100 130 159 219 278 34 44 54 74 95 137 178
05500069 123 144 165 210 252 338 424 86 103 120 154 186 254 321