Manual operation
I
t is possible to test the functions of the unit manually.
Service / Manual operation
Manual operation Settings:
Standard setting:
Description:
Off / De-icing / Damper / Supply air / Extract air /
Vent.+ compressor / Vent. + heating
Off
The functions of the unit can be read off manually.
Off Description: Manual test deactivated (normal operating mode).
De-icing Description: Test of de-icing function.
Supply air Description: Test of supply air.
Extract air Description: Test of extract air.
Vent.+comp. Description: Test of ventilation and compressor.
Vent.+heating Description: Test of ventilation and heating operation. During the
test the heating element receives a 50% signal.
Modbus address
N
ilan's ventilation units have open Modbus communication, and you set the desired Modbus address
here.
The Modbus protocol with all registers can be downloaded from our website.
Service / Modbus address
Modbus address Settings:
Standard setting:
Description:
1 247
30
The Modbus address for the local network is entered
here.