EasyManuals Logo

nilan CTS602 HMI Software Instructions

nilan CTS602 HMI
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #31 background imageLoading...
Page #31 background image
Manual operation
I
t is possible to test the functions of the unit manually.
Service / Manual operation
Manual operation Settings:
Standard setting:
Description:
Off / De-icing / Damper / Supply air / Extract air /
Vent.+ compressor / Vent. + heating
Off
The functions of the unit can be read off manually.
Off Description: Manual test deactivated (normal operating mode).
De-icing Description: Test of de-icing function.
Supply air Description: Test of supply air.
Extract air Description: Test of extract air.
Vent.+comp. Description: Test of ventilation and compressor.
Vent.+heating Description: Test of ventilation and heating operation. During the
test the heating element receives a 50% signal.
Modbus address
N
ilan's ventilation units have open Modbus communication, and you set the desired Modbus address
here.
The Modbus protocol with all registers can be downloaded from our website.
Service / Modbus address
Modbus address Settings:
Standard setting:
Description:
1 247
30
The Modbus address for the local network is entered
here.
VPL28 (English)
BY NILAN
31

Other manuals for nilan CTS602 HMI

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the nilan CTS602 HMI and is the answer not in the manual?

nilan CTS602 HMI Specifications

General IconGeneral
Brandnilan
ModelCTS602 HMI
CategoryFan
LanguageEnglish

Related product manuals