Ecodesign data AIR9 - Heat pump for space heating
Model AIR9
Air-to-water heat pump Yes
Water-to-water heat pump No
Brine-to-water heat pump No
Low-temperature heat pump Yes
Equipped with a supplementary heater Yes
Heat pump combination heater No
Temperature control:
Model CTS602
Class 2
Contribution to seasonal space heating energy efficiency 2%
Item Symbol Value Unit Item Symbol Value Unit
Rated heat output Prated 4,7 kW Seasonal space heating
energy efficiency
ŋ
s
206 %
Declared capacity for heating for part load at indoor tempera-
ture 20 °C and outdoor temperature of T
j
Declared coefficient of performance or primary energy ratio
for part load at indoor temperature 20 °C and outdoor tem-
perature T
j
T
j
= -7 °C
Pdh
4,01 kW
T
j
= -7 °C
COPd
3,20
T
j
= +2 °C
Pdh
2,44 kW
T
j
= +2 °C
COPd
4,95
T
j
= +7 °C
Pdh
1,64 kW
T
j
= +7 °C
COPd
6,53
T
j
= +12 °C
Pdh
1,83 kW
T
j
= +12 °C
COPd
9,69
T
j
= bivalent temperature
Pdh
4,66 kW
T
j
= bivalent temperature
COPd
2,83
T
j
= operation limit tempera-
ture
Pdh
4,66 kW
T
j
= operation limit tempera-
ture
COPd
2,07
For air-to-water heat pumps:
T
j
= -15 °C (if TOL < -20 °C)
Pdh
kW
For air-to-water heat pumps:
T
j
= -15 °C (hvis TOL < -20 °C)
COPd
Bivalent temperature
T
biv
-10 °C
For air-to-water heat pumps:
Operation limit temperature
TOL -10 °C
Cycling interval capacity for
heating
Pcych kW Cycling interval efficiency COPcyc
Degradation co-efficient Cdh 0,99
Heating water operating limit
temperature
WTOL 45 °C
Power consumption in modes other than active mode Supplementary heater
Off mode
P
OFF
0,002 kW Rated heat output Psup 6 kW
Thermostat off-mode
P
TO
0,002 kW
Standby mode
P
SB
0,002 kW Type of energy input
Electri-
cal
Crankcase heater mode
P
CK
0,002 kW
Other items
Capacity control:
Variable compressor
Variable indoor water flow
For air-to-water heat pumps:
Rated air flow rate, outdoors
3000
m
3
/h
Variable indoor temperature
adjustment
For water-or brine-to-water
heat pumps: Rated brine or
water flow rate, outdoor heat
exchanger
m
3
/h
Sound power level, outdoors
L
WA
50 dB
Annual energy consumption
Q
HE
2597 kWh