5.2 Factory settings
All frequency inverters supplied by Getriebebau NORD are pre-programmed with the default setting for
standard applications with 4 pole standard motors (same voltage and power). For use with motors with
other powers or number of poles, the data from the rating plate of the motor must be input into the
parameters P201...P207 under the menu item >Motor data<.
NOTE:
All motor data can be pre-set using the parameter P200. After successful use of this function,
this parameter is reset to
0 = no change! The data is loaded automatically into parameters
P201...P209 – and can be compared again with the data on the motor rating plate.
3~ Mot
IEC 56
IM B3
cosϕ 0,74
cosϕ 0,74
IP55 Rot. KL 16 Th.Cl.F
EN60034
60 Hz 460 V Y
5,2 A
2,5 kW
1765 /min
1440 /min
P206
P201
P204
P203 P202
P200
9,0 / 5,2 A
50 Hz
2,2 kW
P207
P200 Motor list:
0 = no change 8 = 0.37 kW 400V
1 = no motor 9 = 0.50 HP 460V
2 = 0.25 kW 230V 10 = 0.55 kW 230V
3 = 0.33 HP 230V 11 = 0.75 HP 230V
4 = 0.25 kW 400V 12 = 0.55 kW 400V
5 = 0.33 HP 460V 13 = 0.75 HP 460V
6 = 0.37 kW 230V 14 = 0.75 kW 230V
7 = 0.50 HP 230V ....
230 / 400 V
Δ
/
Y
RECOMMENDATION: For the correct operation of the drive unit, it is necessary to input the motor data
according to the rating plate as precisely as possible. In particular, an automatic
stator resistance measurement using parameter P220 is recommended.
In order to automatically determine the stator resistance, P220 = 1 must be set and
confirmed by pressing "OK". The value calculated for the line resistance (dependent
upon P207) will be saved in P208.
ATTENTION
After a default setting "Enable Left" or "Enable Right", the digital inputs DIN2 and DIN3 are
additionally
assigned for the evaluation of an HTL incremental encoder. The encoder evaluation
function cannot be switched off. This means that with the use of an incremental encoder, it is
essential to set parameters (P420[-02]) and (P420[-03]) to "no function". (For using the DIP-
switches of the frequency inverter for parametrisation, please lock at section 5.1.2 .)
NOTE
It must be noted that DIP switch settings on the frequency inverter have priority over the
parameter settings.
In addition, the settings of the integrated potentiometers P1 and P2 must be taken into account.