NORDAC SK 200E Manual
44 Subject to technical alterations BU 0200 GB
2.8.2 Details of the SK 2x5E control connections
Control voltage 24V external! Terminal 44. If the frequency inverter does not have an optional internal mains
unit, it must be provided with an external 24V supply.
For devices in which the AS interface
is used (SK 225E and SK 235E) the control voltage supply must be
via the yellow AS interface cable
. However, in this case, the frequency inverter must not be additionally
supplied via terminal 44, in order to prevent damage to the mains unit or the AS-I bus.
Terminal/
Name
Function
{Factory setting}
Data Description / wiring suggestion Parameter
SK 205E, SK 215E, SK 225E, SK 235E
44 24V external 24V supply
-
40 GND
Reference potential
for digital signals
18VDC ... 30VDC -/+0%
200mA ... 800mA
according to the FI load,
the inputs and outputs and
equipment with options
24VDC, max 60mA
Output voltage with the
use of the AS interface
External supply voltage for the FI
control unit and the DO1 output
For SK 225/235E and use of the
AS-I (yellow cable), the SK 200E is
supplied from the AS-I
-
21 DIN1 Digital input 1
{ON right}
P420 [01]
22 DIN2 Digital input 2
{ON left}
P420 [02]
23 DIN3 Digital input 3
{fixed frequency 1,
(P465[-01])}
P420 [03]
24 DIN4 Digital input 4
{fixed frequency 2,
(P465 [-02])}
Digital input as per
EN 61131-2, Type 1
Low: 0 -5V
(~ 9.5k)
High: 15-30V
(~ 2.5-3.5k)
Input capacitance:
Input 1 + 4 = 10nF
Input 2 + 3 = 1.2nF
Scanning time: 1ms
Reaction time: 4ms
40
44
24
23
22
21
GND
24V
Inputs 1 + 4 react slowly
Inputs 2 + 3 react quickly
P420 [04]
1 DO1 Output 1
{Error}
Digital output
18-30V, each to VI 24V
max. 200mA
max. 100k
Ωload
For evaluation in a control system.
With SK 225/235E and the use of
the AS-i (yellow cable) no load may
be applied to DO1.
P434
38 TF+ PTC resistor input
39 TF- PTC resistor input
-
For monitoring the motor
temperature by PTC.
For separate mounting of the motor
and the FI (cable length), shielded
cable must be used.
-