NORDAC SK 200E Manual
142 Subject to technical alterations BU 0200 GB
6.1.1 Operating displays
The abbreviations used are described in Section 9.12 “Abbreviations in this Manual".
Parameter
{Factory setting}
Setting value / Description / Note Device Supervisor
Parameter
set
P000 Operating parameter display
0.01 ... 9999 In the SimpleBox (SK CSX-3H) display, the parameter value online selected in P100 is
displayed.
P001 Selection of display value
0 ... 63
{ 0 }
0 = Actual frequency [Hz], is the actual output frequency supplied by the FI.
1 = Rotation speed [1/min]
, is the actual rotation speed as calculated by the FI.
2 = Setpoint frequency [Hz]
: the output frequency equivalent to the actual setpoint. This
need not match the actual output frequency.
3 = Current [A]
: the actual output current measured by the FI.
4 = Torque current [A]
: the torque-developing output current of the FI.
5 = Voltage [V~ ]
: the actual alternating voltage being output by the FI.
6 = D.c. link circuit voltage [V =]
: the internal DC voltage of the FI. Amongst other things,
this depends on the level of the mains voltage.
7 = cos Phi,
the currently calculated value of the power factor.
8 = Apparent power [kVA]
: the actual apparent power calculated by the FI.
9 = Real power [kW]: the actual effective power calculated by the FI.
10 = Torque [%]
: the actual torque calculated by the FI.
11 = Field [%]:
the actual field in the motor calculated by the FI.
12 = On-time (operating hours) [h]:
time that voltage is applied to the FI.
13 = Run-time (enabled operating hours) [h]:
time for which the FI has been enabled.
14 = Analog input 1 [%],
actual value AIN1 of the first I/O extension SK xU4-IOE.
15 = Analog input 2 [%],
actual value AIN2 of the second I/O extension SK xU4-IOE.
16 = Position setpoint value ÆPosicon, BU 0210
17 = Position current value Æ Posicon, BU 0210
19 = Temperature of heat sink [°C]: current temperature of the FI heat sink.
20 = Usage rate motor [%]
: average motor load, based on the known motor data
(P201...P209).
21 = Usage rate braking resistor - R [%]
: average braking resistor load, based on the known
resistance data (P556...P557).
22 = Internal temperature [°C]
, current temperature in FI housing.
23 = Motor temperature [°C]
, only in combination with the analog input and appropriate
wiring (KTY84).
30 = Current setpoint value of the motor potentiometer-Setpoint value [Hz]
, display of
the setpoint which can be set in advance (without the drive unit running) via the motor
potentiometer function 71 / 72 (See parameter P420).
50 = Actual incremental encoder position value Æ Posicon, BU 0210
51 = Actual absolute encoder position value Æ Posicon, BU 0210
52 = Actual position difference Æ Posicon, BU 0210
53 = Actual position difference Absolute/Incremental Æ Posicon, BU 0210
54 = Actual position difference Calculated/Measured Æ Posicon, BU 0210
60 = R Stator Ident: stator resistance, automatic determination of motor data, P220
61 = R Rotor Ident: rotor resistance, automatic determination of motor data, P220
62 = L Scatter Stator Ident, stator leakage inductance, from automatic determination of
motor data, P220
63 = L Stator Ident: stator inductance, from automatic determination of motor data, P220