34 Subject to technical alterations BU 0200 GB
1U2 (L11)
1V2 (L21)
1W2 (L31)
PE (PE1)
Line choke SK CI1-460/x-C
1U1 (L1)
1V1 (L2)
1W1 (L3)
Netzdrossel SK CI1-460/x-C
PE (PE2)
L3 (L32)
L2 (L22)
L1 (L12)
Frequenzumrichter
Netzanschluss -
Inverter
Mains supply -
Befestigungselement
4x für M4
Fastening element
Netz Filter-CSA SK CIF-323-40 / SK CIF-340-60 - Montagehinweise
Line Filter-CSA SK CIF-323-40 / SK CIF-340-60 - Installation hints
Optional:
Modifications for on-wall mounting
- Remove fixing screws
- Remove side frames
- Screw on alternate side frames
- Plug fastening elements in
Optional:
Umbau aus Wandmontage
- Befestigungsschrauben lösen
- Seitenteile abnehmen
- Seitenteile für Wandmontage aufsetzen
- Befestigungselemente anstecken
NS 35/7,5
- optional for SK CIF-340-60
- optional für SK CIF-340-60
SK CIF-340-60
SK CIF-323-40
SK CIF-340-60
SK CIF-323-40
2.4.5 Technical data
SK CIF-323-20 SK CIF-323-40
Mains phases 1/3 AC
Mains voltage 1/3~200 … 240 V, ±10%, 47 …63 Hz
Input/Output current max. 20 A max. 40 A
Max. mains fuse 25 A* 60 A*
Ambient temperature 0°C … +50°C
Tightening torque for screw terminals 0.5 … 0.6 Nm 2.5 Nm
Connection facility (flexible) 0.2 … 4 mm² 0.5 … 25 m
Protection class IP20
Weight 0.61 kg 0.74 kg
*Class, type and size of the fuse according to the connected frequency inverters (Section 8.3.5)
SK CIF-340-30 SK CIF-340-60
Mains phases 3 AC
Mains voltage 3~380 V -20% … 500 V +10%, 47 …63 Hz
Input/Output current max. 30 A max. 60 A
Max. mains fuse 100 A* 100 A*
Ambient temperature 0°C … +50°C
Tightening torque for screw terminals 0.5 … 0.6 Nm 2.5 Nm
Connection facility (flexible) 0.2 … 4 mm² 0.5 … 25 m
Protection class IP20
Weight 0.57 kg 0.71 kg
*Class, type and size of the fuse according to the connected frequency inverters (Section 8.3.5)