9.5.4 Reduced output current due to mains voltage
The devices are designed with thermal characteristics according to the rated output currents. Accordingly,
for lower mains voltages, higher currents cannot be taken off in order to maintain the stated power constant.
For mains voltages above 400v there is a reduction of the permissible continuous output current, which is
inversely proportional to the mains voltage, in order to compensate for the increased switching losses.
1.2
0.4
k
Unetz
Unetz()
480320 Unetz
320 340 360 380 400 420 440 460 480
0.4
0.5
0.6
0.7
0.8
0.9
1
1.1
1.2
Mains voltage [V]
I / I
N
9.5.5 Reduced output current due to the heat sink temperature
The temperature of the heat sink in included in the calculation of the reduction of output current, so that at
low heat sink temperatures, a higher load capacity can be permitted, especially for higher pulse frequencies.
At high heat sink temperatures, the reduction is increased correspondingly. The ambient temperature and
the ventilation conditions for the device can therefore be optimally exploited.